11.7.1 Preparation for Maintenance on the Anode Pipe
WARNING!
Danger from chemical residue
Possible consequence: Fatal or very serious inju‐
ries from chemical residue
Measure: During maintenance wear the goggles
and gloves provided.
Ventilate the room during maintenance.
11.7.2 The PVDF Float and Stop Pipe
A1996
2.
1.
Fig. 76: The PVDF float
1.
Tighten the coupling under the anode
2.
Remove the PVDF float and the stop pipe from the anode
pipe.
3.
Clean the PVDF float.
4.
Check the PVDF float for leaks.
5.
Clean the stop pipe.
6.
Replace the PVDF float.
Make sure that the reed switch for "low level" is
correctly adjusted to the PVDF float pipe.
7.
Replace the stop pipe.
During annual maintenance:
During three-yearly maintenance:
Preventative maintenance
97