16
Technical data
Tab. 9: 100 ... 1250 g/h
Capacity
g/h
100 200
300
400
500
600
750
1000
1250
kg/24
h
2.2
4.4
6.6
8.8
11
13.2
16.5
22
27.5
Dimensions
mm
1250x600x1550
1650x600x2000
Space requirement
mm
1850x1500
2250x1500
Transport weight
kg
375
650
Brine tank
Litres 130 130
200
200
200
380
380
380
380
Recommended product
tank
Litres 200 300
400
500
600
700
800
1200
1500
Process data
Number of cell chambers -
1
2
3
4
4
2
3
4
4
Water needed*
l/h
84
88
112
116
145
149
180
190
200
Process water
l/h
4
8
12
16
20
24
30
40
50
Cooling water 20 °C**
l/h
80
80
100
100
125
125
150
150
150
Salt
kg/24
h
5
10
15
20
25
30
35
50
60
Dilution air***
m
3
/h
8
16
24
32
40
47
59
79
99
Product concentration
20 ... 25 g/l
Ambient temperature
10 ... 35 °C
Maximum ambient air
humidity****
85 %
Connectors
Raw water feed
20 mm
Brine for softener
20 mm
Brine for membrane cell
20 mm
Filling the brine tank
20 mm
Product outlet
20 mm
Bleeding, diluted hydrogen*****
63 mm
110 mm
Bleeding, production tank
20 mm
Waste water duct
40 mm
50 mm
Cooling, output
20 mm
Remarks
*
Maximum water hardness = 15 °dH, minimum pressure 2.5 bar
**
Depending on the actual water temperature, maximum 20 °C
***
Ensure minimum dilution to 0.4 % of the lower explosion limit with a fan
****
Non-condensing, non-corrosive and dust-free ambient air in the installation room
*****