If the password protection has been activated, the password must be entered in order
to access the deactivation menu. See the menu structure on page 67.
14.8 Advanced function
The unit gives access to number of advanced functions which can be reached by
answering
“YES“ to the point „ADV.SET“.
Memory (MEM):
In the memory menu you can save the configuration of the device in
the UMU-FD, and then move the UMU-FD onto another device of the same type and
download the configuration in the new device.
Display setup (DISP):
Here you can adjust the brightness contrast and the backlight.
Setup of TAG numbers with 6 alphanumerics. Selection of functional readout in the
line of the display
– choosen between readout of analog output or tag no.
Two-point process calibration (CAL):
The device can be process-calibrated in 2
points to fit a given Input signal. A low input signal (not necessarily 0%) is applied
and the actual value is entered via UMU-FD. Then a high (not necessarily 100%) is
applied and the actual value is entered via UMU-FD. If you accept to use the
calibration, the device will work according to this new adjustment. If you later reject
this menu point or choose another type of input signal the device will return to factory
calibration.
Process simulation function (SIM):
In the menu point
“EN.SIM” it is possible to
simulate an Input signal by means of the arrow keys and thus control the output
signal up or down. If you confirm with , the device jumps back to normal mode. The
following point allows you to activate relay 1 and 2 by means of the arrow-keys
up/down. You must exit the menu by pressing (no time-out). The simulation
function exits automatically, if the UMU-FD is detached.
Password (PASS):
Here you can choose a password between 0000 and 9999 in
order to protect the unit against unauthorized modifications to the configuration. The
unit is delivered default without password.
Language (LANG):
In the menu
”lang.setup” you can choose between 7 different
language versions of help texts that will appear in the menu. You can choose
between: UK, DE, FR, IT, ES, SE and DK.
Auto diagnosis
The device performs an advanced auto diagnosis of the internal circuits.
The following possible errors can by displayed in the front unit UMU-FD.
CJ.ER
-
CJC-sensor defect or temperature outside range
FL.ER
-
Flash error
AO.ER
-
No lead on the current output (only for S4...20 mA / S20...4 mA)
NO.CO
-
Connection error
IN.ER
-
Error levels on input
TY.ER
-
Configuration in UMU-FD does not match this product type