11
promesstec GmbH
I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: [email protected] I Internet: www.promesstec.com
5. Decomposition of the system UMU 100-A-B
First, disconnect dangerous voltage from the terminals.
The device is released from the DIN rail by loosening the lower catch.
When the front LED is red / display shows AO.ER
The device has been developed with a high level of safety. Therefore, a continuous
measurement of the output current takes place at the 4...20 mA output signal. When
the current is 0 mA, the device switches to error mode and the LED indicator lights
red. This function is not a standard option, but must be actively selected in the menu.
The error mode can only be reset by switching the power supply of the device off and
on again.