
39
include damage to cables, excessive number of connections, terminals not made to original
specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose
of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with
the manufacturer
’
s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak
detection equipment. Intrinsically safe components do not have to be isolated prior to working on
them.
3. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring
that this will not exceed the permissible voltage and current permitted for the equipment
in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a
flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only
with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the
atmosphere from a leak.
4. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into account the
effects of aging or continual vibration from sources such as compressors or fans.
5. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
6. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not
be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-
free area.) Ensure that the detector is not a potential source of ignition and is suitable for the
refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant
and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 %
maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing
chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-
work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered
from the system, or isolated (by means of shut off valves) in a part of the system remote from the
leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the
brazing process.
7.Removal and evacuation
When breaking into the refrigerant circuit to make repairs
–
or for any other purpose
–
Summary of Contents for 28964490
Page 1: ...1 Operating instructions Bahag No 28964490 ItemNo JHS A030 09KR2 A W...
Page 24: ...24 PORTABLE AIR CONDITIONER Instruction Manuel...
Page 46: ...46...
Page 47: ...47 I 48 II 51 III 52 IV 55 V 56 VI 58 VII 59 VIII 60 IX 60 X 67 R290 R290...
Page 48: ...48 I 12m2...
Page 49: ...49 50 cm...
Page 50: ...50 8...
Page 51: ...51 35 24 7 35 II LED...
Page 53: ...53 2 3 4 5 6 1 24 7 2 1...
Page 56: ...56 3 2 FULL 3 3 3 4 3 V 1 1 1 1 1 1 2 1 1 2 2 3...
Page 57: ...57 1 2 1 2 45 2 3 1 3 1 50 cm 4 4 5 6 1 2 45...
Page 58: ...58 5 6 280 1500 mm VI 1...
Page 59: ...59 VII EVA EVA EVA 40 104...
Page 60: ...60 VIII 1 2 3 4 5 6 IX 1 1 2 3 4 5 CO2 6...
Page 61: ...61 7 8 9 1...
Page 62: ...62 2 3 4 5 6 LFL 25...
Page 63: ...63 OFN 7 OFN OFN OFN 8 OFN...
Page 64: ...64 9 a b c d e f g h 80 i j k 10 11...
Page 66: ...66 FL 7 35 44 95 17 62 3 ce E2 ce E1...
Page 67: ...67 X...
Page 69: ...69 HORDOZHAT KL MABERENDEZ S Haszn lati utas t s...
Page 91: ...91 P ENOSN KLIMATIZACE U ivatelsk p ru ka...
Page 112: ...112 TRANSPORTABELT KLIMAANL G Brugsvejledning...
Page 133: ...133 PRENOSIVI KLIMA URE AJ Upute za uporabu...
Page 155: ...155 F RANLEG LOFTR STING Lei beiningarhandb k...
Page 176: ...176 DRAAGBARE AIRCONDITIONER Gebruiksaanwijzing...
Page 198: ...198 B RBART KLIMAANLEGG Bruksanvisning...
Page 219: ...219 PRENOSN KLIMATIZA N JEDNOTKA N vod na obsluhu...
Page 240: ...240 Lokal luftkonditionering...
Page 245: ...245 Montering av f nstert tningspl t Avgasr rsmontering...
Page 265: ...265 PRENOSNA KLIMATSKA NAPRAVA Navodila za uporabo...