ProfiHub A5/B5 User Manual 

 

 
 

          _______________________________________________ 

 

 

 

 

 

Version 2.1.1 

– June 2014 

Page 1 / 59 

ProfiHub-A5B5-Manual-EN 

© PROCENTEC 2005-2014 - Copyright - all rights reserved 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

User Manual 

ProfiHub A5/B5 

5 Channel DP Spur and Repeater component 

 
 
 
 
 
 

 

 

 

5 Isolated Channels. 

Transparent for all 

PROFIBUS DP protocols.

 

RS 485 specifications

 for each channel. 

Max. 12 Mbps

Max. 31 devices

 per channel. 

Max. 1200 m spur line length

No limit in serial placement. 

No address

 required. 

Integrated termination facilities. 

Configurable grounding system. 

 

IP 65

 classification (ProfiHub A5). 

IP 20 

classification (ProfiHub B5). 

Summary of Contents for ProfiHub A5

Page 1: ...iHub A5 B5 5 Channel DP Spur and Repeater component 5 Isolated Channels Transparent for all PROFIBUS DP protocols RS 485 specifications for each channel Max 12 Mbps Max 31 devices per channel Max 1200...

Page 2: ...Qualified Technicians Only qualified technicians should be allowed to install and work with this equipment Qualified technicians are defined as persons who are authorized to commission to ground to ta...

Page 3: ...f the ProfiHub can be recycled For further information about environment friendly recycling and the procedure for disposing your old equipment please contact PROCENTEC Klopperman 16 2292 JD WATERINGEN...

Page 4: ...Display 11 1 9 Comparison table 12 2 Installation Instructions ProfiHub A5 26 2 1 Location 26 2 2 Position 26 2 3 Mounting 26 2 4 Power Supply 27 2 5 Backbone 28 2 6 Spur Segments 29 2 7 Termination 3...

Page 5: ...tures with extended spur lines that individually can handle a maximum of 31 devices and a length equal to the main bus The ProfiHub A5 and B5 refresh a received message on one Channel and transfer it...

Page 6: ...s for each channel 9 6 Kbps to 12 Mbps 31 devices per channel 1200 m spur line length depends on transmission speed No limit in serial placement or cascading of ProfiHubs No address required Integrate...

Page 7: ...ured networks Outdoor applications with device and cable stress ProfiHub A5 1 3 Additional Benefits Hot slave insertion and removal during operation Short circuit protection on each Channel Compact an...

Page 8: ...ee the next paragraph 1 5 Grounding System The ProfiHubs can be grounded by 3 methods 1 Direct grounding 2 Indirect grounding through a capacitor 3 Combination of direct and indirect In most cases it...

Page 9: ...1 June 2014 Page 9 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved 1 6 Cable lengths for PROFIBUS DP The cables on the Channels and the Main Channel should comply with the...

Page 10: ...ions for RS 485 Fig 7 The ProfiHub A5 can handle cables based on multiple protection sheaths with a diameter between 6 to 12 mm Fig 8 Parameter Value Wires 2 twisted Impedance 135 165 Ohm at 3 to 20 M...

Page 11: ...eed but has not locked it yet The transmission speed has been detected Main RX OK No communication detected on the Main Channel 1 or more devices communicating on the Main Channel 1 or more devices co...

Page 12: ...ectors see chapter 0 2 Sales offices and Distributors HEADQUARTERS PROCENTEC T 31 0 174 671800 Klopperman 16 F 31 0 174 671801 2292 JD WATERINGEN E in fo procentec com Netherlands I www procentec com...

Page 13: ...in streamlinepm com Canada I www streamlinepm com CHILE RP Ingenieria Limitada T 56 0 41 2469350 Tucapel 92 oficina 52 F 56 0 41 2522592 Concepci n E r odrigopinto rpingenieria cl Chile I www rpingeni...

Page 14: ...GERMANY PROCENTEC GmbH T 49 0 721 831 663 0 Benzstrasse 15 F 49 0 721 831 663 29 D 76185 Karlsruhe E in fo procentec de Germany I www procentec de INDIA UL Engineering Services Software Pvt Ltd T 91 2...

Page 15: ...gashi Gotanda Shinagawa ku Tokyo 141 0022 Japan KOREA Hi PRO Tech Co Ltd T 82 82 31 216 2640 2802 U Tower 1029 F 82 82 31 216 2644 Youngduk dong Giheung gu E c hays hiprotech co kr Yongin Si Kyunggi d...

Page 16: ...Br ila 7 F 40 365 809 305 540331 Tg Mure E s ajgo tibor svt ro Romania I www svt ro SAUDI ARABIA ASM Process Automation T 966 2 691 2741 Al Zahra Dist Attas st F 966 2 682 8943 cross section with hel...

Page 17: ...3400 Burgdorf I www profitrace ch Switzerland TAIWAN Full Data Technology T 886 2 87519941 9097 6F No 200 Gangqian Rd F 886 2 87519533 Neihu District Taipei City E s ales fulldata com tw 114 Taiwan I...

Page 18: ...g illan parkelect co uk BT3 9JU I www parkelect co uk N Ireland UNITED STATES Grid Connect Inc T 1 630 245 1445 1630 W Diehl Road F 1 630 245 1717 Naperville Illinois 60563 E s ales gridconnect com US...

Page 19: ...W Australia 2164 I www profibuscentre com au BELGIUM and LUXEMBOURG Bintz Technics N V T 32 2 720 49 16 Brixtonlaan 23 F 32 2 720 37 50 B 1930 Zaventem E bl oemen bintz be Belgium I www bintz be BRAZI...

Page 20: ...com Egypt I www masautomation com ESTONIA Saksa Automaatika OU T 372 605 2526 Peterburi Tee 49 F 372 605 2524 Tailinn E in fo saksa automaatika ee EE 11415 Estonia I www saksa automaatika ee FINLAND...

Page 21: ...E in fo instrumetrics ic co il Netanya 42170 I www inst ic co il Israel ITALY PROCENTEC Italy T 39 030 200 8610 Via Branze n 43 45 F 39 030 238 0059 25123 Brescia E w ww procentec it Italy W w ww proc...

Page 22: ...1 2292 JD Wateringen E in fo procentec com Netherlands I www procentec com NORWAY AD Elektronikk AS T 47 64 97 60 60 Boks 641 F 47 64 97 60 70 N 1401 SKI E k ai ade no Norway I www ade no PERU Control...

Page 23: ...er Street F 27 11 465 8890 Fourways E s ales idxonline com Johannesburg I www idxonline com South Africa 2191 SPAIN LOGITEK S A T 34 93 588 6767 Ctra de Sant Cugat 63 Esc B Planta 1 E x avier cardena...

Page 24: ...1YY United Kingdom Hi Port Software T 44 0 8452 90 20 30 The Hub 2 Martin Close F 44 0 2392 552880 Lee on Solent E s ales hiport co uk Hampshire PO13 8LG I www hiport co uk United Kingdom iTech T 44...

Page 25: ...________________________ Version 2 1 1 June 2014 Page 25 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved For the up to date list of the Sales Offices and Distributors see...

Page 26: ...A5 can be installed in every position but it is recommended to install it with the cable glands pointing down to create a more reliable protection against moist and dust water compartment and glands I...

Page 27: ...ure To connect the 24V supply to the 4 pin screw type terminal proceed as follows Strip the insulation from the cable or the conductors for the 24V power supply Secure the conductors in the screw type...

Page 28: ...e ProfiHub is not the last device on the bus segment connect the Bus Out cable to the top connector of the Main Channel Fig 11 Pin Layout of the screw terminals Pin A Green wire Pin B Red wire Pin I C...

Page 29: ...ors of Channel 1 to 5 Fig 12 Pin Layout of the screw terminals Pin A Green wire Pin B Red wire Pin I Cable shielding OR Pin Cable shielding Testing If a Channel recognizes valid PROFIBUS messages from...

Page 30: ...the segment the termination should be set to ON Fig 13 The termination of the Channels have been set to ON by default Because it is assumed that the new segment is started at the ProfiHub Fig 13 Don t...

Page 31: ...If it is required that the ProfiHub is locked to a certain transmission speed switch S100 should be set to the required value Fig 14 The switch can be reached by removing the top lid To set the trans...

Page 32: ...2 Position The ProfiHub B5 can be installed in every position but it is recommended to install it with the cables pointing down In this position it is also easier to read the status display 5 3 Mount...

Page 33: ...the power is switched on it can be diagnosed by the following indicators All the LEDs should be shortly blinking The POWER LED is ON The READY LED is ON or Blinking It is recommended to use a power s...

Page 34: ...Spur Segments Connect the spur segments to the connectors of Channel 1 to 5 Fig 17 The second method is to place a PROFIBUS standardized plug on the DB9 connector of the specific Channel Pin layout o...

Page 35: ...s the last device on the bus the termination should be set to ON Fig 18 The termination of the Channels have been set to ON by default Because it is assumed that the new segment is started at the Prof...

Page 36: ...transmission speed by default If it is required that the ProfiHub B5 is locked to a certain transmission speed the baudrate switch should be set to the required value Fig 19 To set the transmission sp...

Page 37: ...rted Protocols Transmission speed Transmission speed detection Transmission speed switch Transmission speed detection time Data delay time Delay time jitter DP V0 DP V1 DP V2 FDL MPI FMS PROFIsafe PRO...

Page 38: ...at 187 5 kbps 400 m at 500 kbps 200 m at 1 5 Mbps 100 m at 3 Mbps to 12 Mbps 6 to 12 mm 2 5 mm2 Stranded or Solid core Maximum 31 per Channel including ProfiHubs OLMs Laptops PCs etc Integrated and sw...

Page 39: ...s Transmission speed Transmission speed detection Transmission speed switch Transmission speed detection time Data delay time Delay time jitter DP V0 DP V1 DP V2 FDL MPI FMS PROFIsafe PROFIdrive and a...

Page 40: ...bps to 12 Mbps 10 mm when the ground rail is used 2 5 mm2 Stranded or Solid core Maximum 31 per Channel including ProfiHubs OLMs Laptops PCs etc Integrated and switchable Powered according to IEC 6115...

Page 41: ...au NSW Australia 2164 I www profibuscentre com au BELGIUM and LUXEMBOURG Bintz Technics N V T 32 2 720 49 16 Brixtonlaan 23 F 32 2 720 37 50 B 1930 Zaventem E bloemen bintz be Belgium I www bintz be...

Page 42: ...3 247 37 95 54 1 rue de la Briaudi re E jy bois agilicom fr Z A La Ch taigneraie I www agilicom fr 37510 BALLAN MIRE France GERMANY PROCENTEC GmbH T 49 0 721 831 663 0 Benzstrasse 15 F 49 0 721 831 66...

Page 43: ...ndustrial Technologies S A L ITEC T 961 1 491161 Point Center Boulevard Fouad Chehab F 961 1 491162 Sin El Fil E sales iteclb com Beirut I www iteclb com Lebanon MEXICO Grid Connect Inc T 1 530 219 25...

Page 44: ...I www idxonline com South Africa 2191 SPAIN LOGITEK S A T 34 93 588 6767 Ctra de Sant Cugat 63 Esc B Planta 1 E xavier cardena logitek es Rub BARCELONA 08191 I www logitek es Spain SWEDEN P L Nordic A...

Page 45: ...Tech T 44 0 1292 311 613 Unit 1 F 44 0 1292 311 578 Dukes Road E sales itech troon co uk Troon I www itech troon co uk Ayrshire KA10 6QR United Kingdom Parkelect Ltd T 44 2890 777743 84 Dargan Road F...

Page 46: ...codes Component Order code Remarks ProfiHub A5 16010 Includes mounting set Ground rail 16011 The ground rail has to be mounted inside the casing to supply a common grounding area for all cable shield...

Page 47: ...is calculated as follows TBit 1 bit baudrate bps Examples 12 Mbps TBit 83 ns 1 5 Mbps TBit 667 ns Busparameters Settings that define the timing behaviour on the bus They are defined in the master Exam...

Page 48: ...he Hub Data frames which were received on one port are transferred to all the other ports chicken foot topology MPI Multiple Protocol Interface Protocol defined by Siemens which uses the layer 1 and 2...

Page 49: ...vent reflections with PROFIBUS DP the termination has to be powered Topology In a communications network the pattern of interconnection between network nodes e g bus ring star configuration PI PROFIBU...

Page 50: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 50 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved 11Certificates...

Page 51: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 51 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved...

Page 52: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 52 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved...

Page 53: ...rsion 0 3 First release Version 0 4 Update of technical information Addition of the ProfiHub B5 first part Version 0 5 Update of technical information Paragraph with ProfiHub A5 B5 comparison Chapter...

Page 54: ...e 54 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved 13Next version Signal amplitudes Capacity of a channel Description of the ground rail Adjustment of busparameters when...

Page 55: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 55 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved 14Notes...

Page 56: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 56 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved...

Page 57: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 57 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved...

Page 58: ...ProfiHub A5 B5 User Manual _______________________________________________ Version 2 1 1 June 2014 Page 58 59 ProfiHub A5B5 Manual EN PROCENTEC 2005 2014 Copyright all rights reserved...