Chapter 7 RUN Mode and Errors
7-21
7.5.4
Clock Setup Error
This message displays when the lithium backup battery’s voltage for the internal clock runs out. To reset the
error, you need to turn the ST’s power OFF and then ON again. Leave the ST ON continuously and the bat-
teryís charge will become sufficient for backup after 24 hours, and will be fully charged in approximately 96
hours. If the battery is incorrectly replaced, the battery may explode. To avoid the danger, please do not
replace the battery yourself. When the battery needs a replacement, please consult with your local ST distrib-
utor.
After changing the backup battery, set up the internal clock.
•
In Hitachi Industrial Equipment System’s HIDIC H (HIZAC H) Series, the error code is divided
into 2 bytes, whereas the ST Error Number is composed of 1 byte codes.
E.g.
When the Display Error Number is 8*, or 5*, use only the left column as the error number.
•
In Toshiba's PROSEC T Series, the Error Code is 4 characters long; on the ST, Error Numbers
are changed to and displayed in Hexadecimal.
•
With the Allen-Bradley PLC-5 and SLC-500 Series, the EXT/STS error codes have been re-
mapped to start at D0 HEX, so they will not conflict with other error codes. When looking up
the error number in the PLC manual, subtract D0 h from the ST error code to find its error value.
E.g.
SEE
6 Initializing the ST (Page 6-1)
•
The lifetime of the backup battery depends on the ambient temperature and the amount of cur-
rent being charged and used. The table below gives a general indication of how long the battery
will last.
Battery Ambient
Temperature
40
o
C or lower
Unit Ambient
Temperature
25
o
C or lower
Expected
Lifetime
10 years or
longer
Expected
Lifetime
10 years or
longer
0 1
0 7
1 7
Reply
Return
Display
Command
Code
Error No.
ST
PLC
Error Code
Error Code
D1
01
EA
1A
Summary of Contents for Pro-face ST Series
Page 1: ...User Manual ST Series...
Page 13: ...12 Memo...
Page 18: ...1 1 1 Introduction 1 1 Prior to Operating the ST 1 2 System Design 1 3 Accessories...
Page 54: ...4 1 4 Data Transfer 4 1 Serial Data Transfer 4 2 Ethernet Data Transfer...
Page 61: ...ST Series User s Manual 4 8 Memo...
Page 123: ...ST Series User s Manual 7 24 Memo...
Page 124: ...8 1 8 Maintenance 8 1 Regular Cleaning 8 2 Periodic Check Points 8 3 Changing the Backlight...