![Pro-face PL-DU6900 User Manual Download Page 33](http://html1.mh-extra.com/html/pro-face/pl-du6900/pl-du6900_user-manual_1605191033.webp)
Chapter 4 - Installation and Wiring
4-2
PL-DU6900/PL-DU7900 User Manual
Create the correct sized opening required to install the DU, using the installation
dimensions given. The moisture resistant gasket, installation fasteners and attach-
ment screws are all required when installing the DU.
2.4 Display Unit Dimensions
Creating a Panel Cut Out
4.2
DU Installation
4.2.1 Installation
Confirm the Installation Gasket’s Seating
• Check that the installation panel or cabinet's
surface is flat, in good condition and has no
jagged edges.
• Panel thickness should be from 1.6mm to
10.0mm.
• Be sure to consider the weight of the DU when
designing the panel.
Be sure the gasket is in place before installing the DU.
Panel
Cut Out
1.6mm to 10.0mm
It is strongly recommended that you use the gasket.
Place the DU on a level surface with the display panel facing downward. Check
that the DU’s installation gasket is seated securely into the gasket’s groove, which
runs around the perimeter of the panel’s frame.
For more information about installing the gasket, refer to
5.1.2 Installation Gasket Replacement
Installation
Gasket
Rear
face
To enhance the DU’s maintainability, operability and ventilation, allow at least 50mm
clearance between the DU and any other objects. (The clearance must be large enough
to allow you to insert or remove expansion boards and to attach connectors.)
Rear View
Side View
50mm
50mm
50mm
50mm
50mm
50mm
50mm