![Pro-face GP-4200 Series Hardware Manual Download Page 142](http://html1.mh-extra.com/html/pro-face/gp-4200-series/gp-4200-series_hardware-manual_1605189142.webp)
Installation and Wiring
142
Connecting the AC Power Cord
NOTE:
The shield ground (SG) and FG terminals are connected internally in the GP
unit unit.
AC Power Cord Preparation
z
Make sure the ground wire is either the same or heavier gauge than the power
wires.
z
Do not use aluminum wires in the power supply’s power cord.
z
Field wiring terminal marking for wire type (75°C [167 °F] copper conductors
only).
*1
To prevent a short circuit caused by loose screws, use a crimp-type terminal with
an insulating sleeve.
WARNING
EXCESSIVE ELECTROMAGNETIC INTERFERENCE
z
When the functional ground (FG) terminal is connected, be sure the wire is
grounded. Not grounding the GP unit can result in excessive Electromagnetic
Interference (EMI). Grounding is required to meet EMC level immunity.
z
Remove power before wiring the GP unit’s power terminals.
z
The AC model is designed to use 100 Vac to 240 Vac input. Using any other
level of power can damage both the power supply and the GP unit.
z
Since the GP unit is not equipped with a power switch, be sure to connect a
power switch to the power supply.
z
Be sure to ground the GP unit’s FG terminal.
Use the following torque to tighten the terminals:
z
Terminal Block: 1.4 N•m (12.4 lb•in.)
z
Functional Ground (FG) Terminal: 1.4 N•m (12.4 lb•in.)
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
AC Power Cord
Grounding Wire
Power Cord
Double-insulated Wire
0.75 to 3.5 mm
2
(18-12AWG)
0.75 to 3.5 mm
2
(18-12AWG)
Recommended Ring
Terminal
*1
J.S.T Mfg. Co., Ltd compatible:
z
V1.25-M4 (18-16AWG)
z
V2-P4 (16-14AWG)
z
V5.5-S4 (14-12AWG)
(1)
φ
4.3 mm (0.17 in.) or more
(2) Less than 7.2 mm (0.28 in.)
J.S.T Mfg. Co., Ltd compatible:
z
V1.25-M4 (18-16AWG)
z
V2-P4 (16-14AWG)
z
V5.5-S4 (14-12AWG)
(1)
φ
4.3 mm (0.17 in.) or more
(2) Less than 7.2 mm (0.28 in.)
Summary of Contents for GP-4200 Series
Page 1: ...3 6HULHV DUGZDUH 0DQXDO...
Page 10: ...10...
Page 42: ...Parts Functions 42...
Page 58: ...Specifications 58 Dimensions External Dimensions 1 Front 2 Right Side 3 Top PP LQ...
Page 110: ...Specifications 110 External Dimensions GP 4501TW 1 Front 2 Right Side 3 Top PP LQ...
Page 134: ...Specifications 134...
Page 161: ...GP4000 Series Hardware Manual 161 1 USB clamp 2 USB cable 2 1 1...
Page 162: ...Installation and Wiring 162...