2.4.
Interface
2.4.1.
Serial Interface
The SP5000 series has a COM port on the side of box module.
The pin array and the shapes of the plug and the socket differ between GP-3600T
COM2 port and SP-5B10 (Power box)/SP-5B00 (Standard box) COM port. The PLC
connection cable that used to be connected to GP3000 Series via its COM2 port
cannot be used as it is. For details, refer to “
”. Cabl
es other than that can be used as they are.
When both the COM1 port and the COM2 port have the RS-422/485 setting, only
the COM2 port can be used for RS-422/485 connection after replacement to
SP-5B00(Standard box).
2.4.2.
Auxiliary I/O Interface (AUX)
SP-
5B10(Power box) has ‘Auxiliary I/O Interface (AUX), but either Alarm Output
or Buzzer Output can be used (Alarm Output and Buzzer Output can be switched
to each other on GP-Pro EX.). Note that RUN Output and External Reset Output
that used to be used for GP-3600T cannot be used anymore.
2.4.3.
Sound Output Interface
If sound output is needed, select SP-5B10(Power Box) and use AUX I/F.
When using Speaker Output, the output value has increased from 70mW to
300mW, so customers using an amplifier should be aware of it.
2.4.4.
FLEXNETWORK interface, FLEXNETWORK interface, CANopen interface,
DIO interface
When GP3000 series (C Class) DIO model, FLEXNETWORK model and CANOpen
model was used, SP-5B10 (Power BOX) is required.
For SP5000 series, below module is required.
GP3000 Series (Control model)
Unit for SP-5B10
(Power box)
DIO Model
AGP3600-T1-AF-D81C
AGP3600-T1-D24-D81C
AGP3600-T1-AF-D81K
AGP3600-T1-D24-D81K
FLEXNETWORK Unit
(Model No. PFXZCHEUFN1)
For more details, refer to
FLEXNETWORK Model
AGP3600-T1-AF-FN1M
AGP3600-T1-D24-FN1M
CANopen Model
AGP3600-T1-AF-CA1M
AGP3600-T1-D24-CA1M
CANopen Master Unit
(Model No. PFXZCHEUCAM1)
For more details, refer to
SP-5B00 (Standard Box) cannot be used for expansion unit.