44
7.3 RS485
7.3.1 About RS485
A typical RS485 connection is as below.
Some Noteworthy Points:
1.
Wires between devices and computer shall be twisted.
2.
Maximum allowable wire length is 1000 meters.
3.
The terminal-end device should have a terminal resistor.
4.
Due to multiple connections, each individual device should be
assigned an IP address as to send/receive.
7.3.2 Connecting RS485
Wiring Diagram
RS232 to RS485 board or
External data logger
T/R -
T/R +
Pin:On
T/R - ↔ T/R1 -
T/R + ↔ T/R1 +
RS232 Cable
Pin:Off
Pin:Off
RS485<->RS232
Inverter (2)
RS485 connector
ON
1
Inverter (1)
RS485 connector
ON
1
Inverter (last)
RS485 connector
ON
1
Connecting to device or computer
with RS485 interface