14
Compliance and Safety Symbols
Safety symbol
Description
There are residual voltages in the PV inverter. It needs 5
minutes to finish discharge.
The PV inverter must not be touched when in operation. Its
enclosure and heat sinks are extremely hot.
Electrical shock! This part is charged. Only qualified and / or
trained electrical technicians are allowed to perform operations
on the inverter.
Please read the User Manual carefully before installing the PV
inverter.
PV-3000S-V/PV-3600S-V/PV-5000S-V/PV-5000S-HV apply to wall-mounting installation,
as described below in detail.
4.1
Determining the Installation Position
【
Basic Requirements
】
The inverter is protected to IP65 and can be installed indoors or outdoors.
PV-3000S-V/PV-3600S-V/PV-5000S-V/PV-5000S-HV weight and dimension as shown in
Table 4.1. The installation method and position must be appropriate for the weight
and dimensions of the inverter.
Do not install the inverter in a place where personnel are likely to come into contact
with its enclosure and heat sinks because there parts are extremely hot during
operation.
Do not install the inverter in an area that stores flammable or explosive materials.
Table 4.1 Weight and dimension table
Inverter model
PV-3000S-V/PV-3600S-V
PV-5000S-V/PV-5000S-HV
Weight (kg)
9
13
Dimensions (W x H x D)(mm)
285 x 336 x 125
335 x 426 x 125
【
Installation Environment Requirements
】
The ambient temperature must be below 45
o
C which ensures the inverter’s optimal
operation and extends its service life.