Initial Setup Guide cBlade ES
4-6
Release 5.0
Table 4.4 Electrical Specifications — 30-Amp BladeFrame
BF200
Note:
If you are installing the BladeFrame BF200 outside of North
America, the appropriate power cord is available in the
Internationalization kit. Contact Fujitsu Siemens Computers
customer support.
Power
Connections
The power switch is located on the connector panel at the rear of the
BladeFrame BF200 chassis. See Figure 4.1 and Figure 4.2 for
locations on the 20-amp and 30-amp chassis options.
Parameter
Description
Rating/Value
Input Voltage
Voltage range
200-240 VAC, auto-ranging
Input Frequency
AC input power
frequency range
47-63 HZ, single phase
Input Current
Maximum current
rating
24 amps RMS at 200 volts
Power
Consumption
System power
range
500 watts minimum to 4,800
maximum
BTU Rating
System total
1,750 minimum to 16,390
maximum
Connector Type
North America
NEMA L6-30P
Connector Type
International
IEC 309 - 24 amp