Prima Klima BLUELINE PK400/450-EC Instructions Download Page 1

Prima Klima Trading CZ, s.r.o.,  Zámostí 594,  CZ-33828 Radnice u Rokycan,  Czech Republic,  

[email protected]

,  Tel.: +420 371 795 340   

www.primaklima.com 

    

EN – Instructions for PK400/450-EC BLUELINE Ventilator 

Article Code

 

m

3

/h

 

Hz 

Power(W) 

dB 

Volts 

Max. temp. 

Weight 

PK400/450-EC 

8000 

50/60 

1,44kW 

85* 

200-277 

40°C 

28,20 Kg 

*maximal noise ratio from the motor without housing

 

Features: 

- ZIEHL-ABEGG motor 

- Low noise emissions 
- Non-stop operation, over 80.000 hours 

- Galvanized steel housing 
- Controllable with 0-10V signal  

- Junction box with Schuko power cable 

 

Safety Information 

This machinery must not be put in operation until prior to reading mounting instructions and safety information. All fans are intended for 
transportation  of  air  in  air  handling  systems

If  installed  in  non-heated  rooms,  the  fan  casing  has  to  be  insulated  in  order  to  avoid 

condensation

They are meant to be used after building them into machines or duct systems or after contact protection grid have been 

installed. (EN ISO 13857)

Fans with duct connections must be connected to ducts on both sides (inlet/outlet). When there is a risk of 

water entering the motor

via the ducts, external protection is required. No moving parts shall be accessible after installation. The fans 

are not to be used in hazardous environments or connected to flue ducts

The fans must not be installed outdoors

,

 (with exception of 

roof fans and fans with, for this purpose, corresponding IP class). If the fans are installed without insulation in non

-

heated areas there is a 

risk  of  condensation.  Safety  accessories  (i.e

motor  protection,  safety  grille)  may  not  be  dismounted,  short  cut  or  disconnected. 

CAUTION! Before service or maintenance, switch off power, (all-pole circuit breaker), and make sure the impeller has come a standstill. 

CAUTION! The fans can have sharp edges and corners which may cause injuries

.

 CAUTION! Be careful when opening the fans service-

hatches (swing-out)

the fan and motor assembled on the hatch is relatively heavy

 

This appliance may be used by children under 8 years of age and older and persons with reduced physical, sensory or mental abilities or 

lack  of  experience  and  knowledge  when  supervised  or  instructed  to  use  the  appliance  in  a  safe  way  and  understand  the  potential 
hazards.  Children  should  not  play  with  the  appliance.  Cleaning  and  maintenance  performed  by  the  user  must  not  be  carried  out  by 

children without supervision.

 

 

Transportation and Storage 

All fans are packaged at the factory to withstand normal transport handling

When handling the goods use suitable lifting equipment in 

order to avoid damage to fans and personnel. Do not lift the fans by the connecting cable, connection box, impeller or inlet cone. Avoid 

blows and shock loads. Store the fans in a dry place protected from weather and dirt until final installation

.

 

 

Operation 

Before initial operation, check the following

- Electrical connection has been properly completed

- Protective conductor has been connected. 
- Motor protection installed. 

- Safety devices in place (protection grid) 
Leftover installation materials and foreign materials have been removed from the casing

.

 

 
When putting into operation, check the following: 

- Connection data corresponds to the specifications on the nameplate

Maximum v6%, -10%, according to IEC38. 

 

Rated  current  must  not  be  exceeded  with  more  than

 

5%  at  rated  voltage.  CAUTION!  When  the  speed  is  regulating

 

by  reducing  the 

voltage the motor current may exceed the rated

 

current at a lower voltage. In this case the motor windings are

 

protected by the thermal 

contact. The minimum static fall

 

of pressure must be observed. 

- The direct

i

on of rotation should correspond to direction-of rotation arrow

.

 

- Smoothness of motor operation

 

(no abnormal noises). 

- Fans must only be operated by a person that has sustainable knowledge or education within this field or handling must be carried out 
with the supervision of such person. 

 

Maintenance, Service and Repair

 

Before maintenance, service or repairs make sure that

- Power supply is interrupted (all-pole circuit breaker). 

- Fan impeller has come to a complete standstill 
- Observe personnel safety regulations! 
 

The fan should be cleaned when necessary

at least once per year to avoid imbalance and unnecessary damage to the bearings. A filter 

will prolong the time interval between each cleaning of the fan

(It is sometimes recommended to install a filter guard). The fan bearings 

are maintenance free and should only be replaced if damaged. Do not use a high-pressure cleaner (steam jet) when cleaning the fan

Make sure the fan impeller's balance weights are not moved or the fan impeller distorted

Listen for abnormal operating noise. 

 