Price STO/R Quick Start Manual Download Page 1

All Metric dimensions ( ) are soft conversion.  

© Copyright E.H. Price Limited 2006. 

Imperial dimensions are converted to metric and rounded to the nearest millimetre. 

In today’s life safety products markets, 

many building codes require fire dampers, 

smoke dampers and combination fire and 

smoke dampers to be inspected for proper 

operation. Many of these codes require 

that the damper be inspected and cycled 

every 6 months to a year depending on the 

local authority and the type of system in 

which it is installed. Usually fire dampers 

and combination fire and smoke dampers 

are supplied with a fusible link. The fusible 

link is a one time device and is generally 

limited to 165°F or 212°F. Once the link has 

experienced these elevated temperatures, it 

can no longer be used and must be replaced 

with an identical link. Locating and acquiring 

FSD DAMPER STO/R OPERATION

Switch is in Normal (Damper Open) Position: 

Damper motor is energized until thermostat 

senses temperature above initial closure 

rating. Above temperature closure rating, 

the damper motor is de-energized and 

damper closes.
Smoke Detector (if used) wired in series with 

temperature sensitive device.
Switch in Closed Position damper motor is 

de-energized and damper is closed.
Detailed wiring diagrams including termi-

nal designation and/or wire color coding 

furnished with each shipment.

Indicator Switch Electrical

Limitations
Installation:

• 

10 Amperes, 1/4 HP, 120 or 240 Volts 

A.C.

•  .5 Ampere, 125 Volts D.C.
•  .25 Ampere, 250 Volts D.C.
•  5 Amperes, 120 Volts (Lamp Load)
•  15 Amperes, 24 Volts D.C.

STO/R Package - Single Thermostat Operator Release

the identical fusible link can be troublesome 

and time consuming. PRICE’s STO/R option 

provides the ease of operating and resetting 

the damper in a matter of seconds without 

replacing the link. The is used in lieu of a 

conventional fusible link. It is a reusable/

resettable heat responsive device that can 

only be reset after a visual inspection of the 

damper. 

Dampers which allow remote 

resetting of the damper from a remote 

location are dangerous. 

A remotely reset 

damper may not be fully functional and 

should be visually inspected. The STO/R is 

reset from the outside of the damper sleeve, 

therefore requiring a visual inspection of 

the damper. By depressing a button on the 

outside of the sleeve an inspector can verify if 

the damper is fully operational. The STO/R is 

a multi-use heat responsive device. It is wired 

in series with the smoke detector therefore 

it is user friendly in most applications. When 

the smoke detector interrupts the current to 

the damper, the STO/R will not hinder the 

closing of the damper. The STO/R package 

includes blade indicator switches which al-

low for remote notification of damper blade 

position, as a standard feature.
The STO/R option is available on all PRICE 

Model FSD Combination Fire/Smoke Damp-

ers and Motorized Multi-Blade Fire Dampers.

Manufacturer’s Recommendations

All moving parts of the damper must be 

inspected and cycled at intervals not greater 

than every six months and in accordance 

with the latest edition of NFPA 90A, 92A, 

local codes and the actuator manufacturer. 

In addition, fuse links shall be removed and 

inspected for corrosion. Dry lubricants are 

recommended.

Single Thermostat Operator Release (STO/R)

for Fire/Smoke Dampers &

Motorized Multiblade Fire Dampers

Jul / 06  245082  SHEET 1 OF 4

Reviews: