MA-5191A
21-10-2021
29 / 110
o
LOCAL IP: 100.0.0.1
The REMOTE IP will be modified according to the installation site.
The LOCAL IP mode is accessed by pressing and holding BT1 for 10s (with the
charger running); the unit will indicate that it has entered LOCAL IP by flashing
all LEDs.
From local IP mode, you can return to REMOTE IP mode in two ways:
o
Press the button again for 10s.
o
By time. The charger automatically switches to the REMOTE IP after 20
minutes in LOCAL IP mode.
10.
PROCESSES:
10.1.1.1
ALARMS:
The following table shows the alarms available in this equipment and the logic associated with
each one of them:
Alarm Name
Status Function logic
Urgent failure
NC
- In normal operation of the charger the contact is open.
-Timed on and off (5sec).
-Closes if:
-No battery connected.
-Battery Test Failure.
-Defective or deteriorated battery.
-Urgent internal rectifier failure.
-Equipment temperature out of range.
End of autonomy
NA
-In normal operation of the charger the contact is open.
-Timed on and off (15sec).
-Closes when the battery is discharging and the voltage drops to the
minimum set value
Network failure
NA
-In normal operation of the charger the contact is open.
-Timed on and off (5sec).
-Closes if the AC mains voltage is out of range or there is no AC.
Non-urgent failure
NA
- In normal operation of the charger the contact is open.
-Timed on and off.
-Closes if:
-Battery overvoltage is measured.
-Temperature sensor error.
-Voltage of outputs 1, 2 or 3 out of range.
-Battery temperature out of range.