Therefore, it is always possible to access the equipment for configuration
by connecting to it through the LOCAL IP even if the REMOTE IP configured
is unknown.
Ways to change the active IP:
-
Switch to LOCAL IP: the equipment must be switched on and running. In
addition, the button must be kept pressed for 10s.
When the charger is in this mode, all the LEDs flash at the same time.
Figure 12. Button and LEDs.
- Return to REMOTE IP. This can be done in a variety of ways:
o
Press the button again for 10s.
o
By time. The charger automatically switches to the REMOTE IP after 20
minutes in LOCAL IP mode.
5.1.1.9
TEMPERATURE SENSOR
The EDT-150-5191charger incorporates a pre-wired temperature sensor to measure the
ambient temperature near the batteries in order to optimise battery life.
By compensating the output voltage with temperature, these chargers maximise the lifetime
of the batteries used.
The features of the sensor are shown below:
FEATURES
Dimensions
39 x 16 x 2 mm (Width x Height x Depth)
Operating temperature
-40 to 80 ºC
Storage temperature
-40 to 80 ºC
Wiring length
2 metres (maximum: 10m)
1
Note 1: The pre-wired sensor can be supplied in other lengths on request:
Standard sizes of 5m and 10m available.
5.1.1.10
CONFIGURATION:
The charger parameters can be configured via an XML configuration file and/or via a web
browser. In addition, the parameters can only be modified within the range established for
each one of them.