P/N 96P557A06        07/02

Dual Capacity, 3 to 6 Tons, R410A
Installation and Maintenance Manual

 WARNING: 

Before performing service or maintenance operations on a system, turn off main

power switches to the indoor unit. If applicable, turn off the accessory heater power switch.
Electrical shock could cause personal injury.

Installing and servicing heating and air conditioning equipment can be hazardous due to system

pressure and electrical components. Only trained and qualified service personnel should install, repair

or service heating and air conditioning equipment.

Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning

and replacing filters. All other operations should be performed by trained service personnel. When

working on heating and air conditioning equipment, observe precautions in the literature, tags and labels

attached to the unit and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing

operations and have a fire extinguisher available.

Move units in the normal “up” orientation. Horizontal units may be moved and stored per the

information on the carton. Do not stack more than three units in total height. Vertical units may be stored

one upon another to a maximum height of two units. Do not attempt to move units while stacked. When

the equipment is received, all items should be carefully checked against the bill of lading to be sure all

crates and cartons have been received. Examine units for shipping damage, removing the units from the

cartons if necessary. Units in question should also be internally inspected. If any damage is noted, the

carrier should make the proper notation on the delivery receipt, acknowledging the damage.

Moving and

Storage

Model

Nomenclature

Table of

Contents

Model Nomenclature  1
Safety Considerations 1
Moving and Storage  1
Physical Data  2
General Installation Information  2-5
Closed Loop Ground Source Systems  6-7
Open Loop Groundwater Systems 8-9
Desuperheater Connection  10-11
Initial Desuperheater Start Up  12
Electrical Connections  12-13
Wiring Schematic  14-15

Unit Electrical Data 16
Electronic Thermostat  16
Microprocessor Control Operation  16-19
Blower Speed  19
ECM Fan Performance Data  19
Unit Start-Up  20-21
Preventive Maintenance  22
Troubleshooting  22-23
Unit Operating Pressures  23
Replacement Procedures  23

Safety

Considerations

Model Type

Premier - R410A

Unit Capacity

MBTUH

Discharge Air Configuration

T = Top Discharge Vertical
B = Bottom Discharge Vertical
E = End Discharge Horizontal
S = Side Discharge Horizontal

Return Air Configuration

L =  Left
R = Right

Voltage

1 = 208-230/60/1

Hot Water Options

0 = None
1 = Hot Water Generation With

Factory Installed Pump

E

T

048

L 1 0 1 C B D S S A

Vintage

A = Current

Non-Standard Option Details

Non-Standard Options

Filter Options

D =1” Pleated Disposable

Sound Kit

B = Blanket (standard)

Coax Options

C = Copper
N = Cupronickel

Blower Options

1 = ECM Blower
2 = Oversized ECM Blower Option

(048 Only)

E Series

Summary of Contents for E Series

Page 1: ...hould be carefully checked against the bill of lading to be sure all crates and cartons have been received Examine units for shipping damage removing the units from the cartons if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Moving and Storage Model Nomenclature Ta...

Page 2: ...s to prevent damage from frozen water lines and excessive heat that could damage electrical components General Installation Information MODEL E036 E048 E060 E072 Fan Wheel 11 X 10 11 X 10 11 X 10 11 X 10 Fan Motor ECM 1 2 ECM 1 2 ECM 1 ECM 1 Compressor Air Coil Dimensions 28 x 25 32 x 25 36 x 25 36 x 25 Area sq ft 4 9 5 6 6 3 6 3 Rows 3 3 3 3 R410A oz 61 0 77 0 100 0 103 0 Weight lbs 320 0 336 0 3...

Page 3: ... normally suspended from a ceiling by six 3 8 diameter threaded rods The rods are usually attached to the unit by hanger bracket kits furnished with each unit Lay out the threaded rods per the dimensions in Figure 2 Assemble the hangers to the unit as shown Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel When attaching the hanger rods to t...

Page 4: ...termine the flow rate These ports should be located adjacent to the supply and return water connections on the unit The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant to water heat exchanger See Table 2 on page 21 for water flow and pressure drop information All source water connections are swivel piping fittings that accept a 1 male pip...

Page 5: ...ION Set the freeze protection switch SW2 2 on the printed circuit board for applications using a closed loop antifreeze solution to LOOP On applications using an open loop groundwater system or closed loop no antifreeze set this dip switch to WELL the factory setting See schematics on pages 14 and 15 CONDENSATE DRAIN On vertical units the internal condensate drain assembly consists of a drain tube...

Page 6: ...he loop pump motor s if applicable to allow trapped air to be discharged and to ensure that the motor housing has been flooded Ensure that the loop flow center provides adequate flow through the unit by checkingthe pressure drop across the heat exchanger and comparing it to the figures shown in Table 2 on page 21 Usually 2 5 to 3 gpm of flow per ton of cooling capacity is recommended in earth loop...

Page 7: ...F P N 96P090A04 GeoLink Flow Center WF Ground Loop Connector Kits with Armaflex CK4S or CK4L GeoLink Polyethylene w Armaflex Insulation Disconnects If Applicable Unit Power Figure 7 Premier Slave Hook up Pump slaving connection for multiple units sharing one flow center Shut Down C C SL2 In SL2 Out Shut Down C C SL1 In SL1 Out SL2 In SL2 Out SL1 In SL1 Out Premier E Unit 1 Premier E Unit 2 With pu...

Page 8: ... loop applications In dual capacity units stage 1 is half of the total tonnage Therefore on a E048 the stage 1 solenoid should flow 3 6 gpm and stage 1 2 together should flow 6 9 gpm Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways depending on local building codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local...

Page 9: ...nd one pilot operated solenoid valve BPV100 or PPV100 1 CC CCHI Premier E series Dual Capacity Logic Board CC GND CCLO Wh Red SV2 Stage 2 BPV100 or PPV100 solenoid valve 3 CCH CCL Blk Blk 2 Remove Typical Two Stage external 24V water solenoid valves type PPV100 or BPV100 wiring CC CCHI CCH CCL Blk Premier E series Dual Capacity Logic Board CC GND CCLO SV1 Wh Red Stage 2 solenoid valve SV2 Blk Blk ...

Page 10: ...r heater 2 Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors 3 Close the cold water inlet valve to the water heater tank 4 Drain the tank by opening the valve on the bottom of the tank then open the pressure relief valve or hot water faucet 5 Flush the tank by opening the cold water inlet valve to the water heater to free the tank...

Page 11: ......

Page 12: ...in the desuperheater water circulating circuit are open 2 Turn on the Premier E unit to first stage heating 3 The DHW pump should be running Be sure the disable switch for the DHW pump SW4 is ON The DHW OFF LED on the unit should not be illuminated 4 The temperature difference between the water entering and leaving the desuperheater should be 5 F to 15 F The water flow should be approximately 0 4 ...

Page 13: ...red for 230 volt operation There is a switch located on the control box which allows the installer to select 208 volt unit operation Refer to Figure 13 on page 13 for switch location UNIT POWER CONNECTION Connect the incoming line voltage wires to L1and L2 of the contactor as shown in Figure 13 below Consult the Unit Electrical Data section on page 16 for correct fuse size EXTERNAL LOOP PUMP POWER...

Page 14: ... 8 C SL1 In SL1 Out 1 2 3 4 5 6 7 C P2 Down C Shut SL1 In SL1 Out 1 2 3 Acc Com Acc NC Acc NO Status LED PCB 17P503A01 Rev A R R R R R G Y R 1 2 3 4 5 Black Violet Yellow Blue Gray T T Brn Premier E Series Main Logic PCB 17P513A05 Not Used NOTE 6 240V L2 2 3 1 Stage 1 Stage 2 Ext Pump 1 2 hp Total 208 230 60 1 Pump Pump G Blk Wh NOTE 4 L1 Gray Wh L2 PB BRISTOL DUAL CAPACITY HIGH CAPACITY Violet Ta...

Page 15: ... CCHI On Off SW2 On Off SW3 N O CR4 Com N O CR3 Com N C CR2 Loop Pump N O CR1 DHW Pump N O Microprocessor 17P547A01 P4 1 2 3 1 2 3 P3 ACC NC ACC COM ACC NO P1 1 2 3 4 5 6 7 8 R C Y1 Y2 G O W L 2 3 4 5 P2 6 7 1 Shut Down C C IN Out IN SL2 Out SL1 SL1SL2 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 1 2 3 4 5 Thermistor Light emitting diode Green Relay coil Capacitor w bleed resistor Switch Condensate ...

Page 16: ...0 seconds after the Y1 input Heat 2nd Stage Y1 Y2 The compressor is de energized immediately the second loop pump is energized 5 seconds after the Y2 input and the hot water pump is cycled 30 seconds after the Y2 input The fan changes to high speed 45 seconds after the Y2 input and the compressor is energized on high capacity 60 seconds after the Y2 input Heat 3rd Stage Y1 Y2 W The hot water pump ...

Page 17: ... thermostat the fan will remain on low speed for 30 seconds at the end of each heating cooling or emergency heat cycle LOCKOUT CONDITIONS During lockout mode the appropriate unit and thermostat lockout LEDs will illuminate The compressor loop pumps hot water pump and accessory outputs are de energized Unless the lockout is caused by an ECM2 low RPM fault the fan will continue to run on low speed a...

Page 18: ...for cooling in the dehumidification mode 5 Auxiliary Off This dip switch disables heating 3rd stage Full emergency heat would in any event still be available if needed 6 Diagnostics Inputs This dip switch allows viewing the inputs from the thermostat to the control board such as Y1 Y2 O G W SL1 In SL2 In on the LED display 7 Diagnostics Outputs This dip switch allows viewing the outputs from the c...

Page 19: ...700 1850 2000 2200 2300 2400 w 1 hp L M H E060 0 75 750 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 L M H E072 0 75 750 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 L M H Factory settings are at recommended L M H DIP switch locations CFM is controlled within 5 up to the maximum ESP M H settings must be located within boldface CFM range Max ESP includes allowance for wet coil and...

Page 20: ...ontrol signal to energize the blower motor Check blower operation 2 Initiate a control signal to place the unit in the cooling mode Cooling setpoint must be set below room temperature 3 First stage cooling will energize after a time delay 4 Be sure that the compressor and water control valve or loop pumps are activated 5 Verify that the water flow rate is correct by measuring the pressure drop thr...

Page 21: ......

Page 22: ...ssary Units should never be operated without a filter Condensate Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick up lint and dirt especially with dirty filters Inspect twice a year to avoid the possibility of overflow Air Coil The air coil must be cleaned to obtain maximum performa...

Page 23: ...ing No Desuperheater Heating No Desuperheater Entering Water Suction Discharge Water Air Suction Discharge Water Air Water Flow Pressure Pressure Super Sub Temp Temp Pressure Pressure Super Sub Temp Temp Temp F GPM TON PSIG PSIG heat cooling Rise F Drop F DB PSIG PSIG heat cooling Drop F DB Rise F 30 1 5 64 72 285 320 11 16 13 19 5 7 15 21 3 0 68 76 290 325 11 16 13 19 3 5 17 23 50 1 5 117 123 225...

Page 24: ...ations without notice WaterFurnace and Premier are registered trademarks of WaterFurnace International Inc 2002 WaterFurnace International Inc Dual Capacity 3 to 6 Tons R410A Installation and Maintenance Manual 9000 Conservation Way Fort Wayne IN 46809 9794 Phone 1 260 478 5667 or 1 800 222 5667 FAX 1 800 783 5667 http www waterfurnace com E Series ...

Reviews: