Preferred JC-10D2 Installation & Operation Instructions Download Page 1

SDI-JC-10D2   rev 11-17-21 

 

page 1  of  12

 

Preferred  Utilities Mfg Corp 

Preferred Instruments div. 

31-35 South Street, Danbury CT 06810 

203-743-6741  

www.preferred-mfg.com

 

JC-10D2 

Process Bargraph Indicator 

with Alarm Relays and Flow Totalizer 

Installation & Operation Instructions 

 

JC-10D2  Features  

 

Field selectable Input Signals: 
   4-20mA, J T/C, K T/C, 10k Thermistor, 0-10V, 0-5V, 0-2.3V 

 

Signal Integrator/Totalizer for Flows, kW, etc with Reset 
with Squre Root and Low Flow Cutoff features, 
Non-Volitale value storage (no batteries or capacitors)  

 

Configurable Dual Alarms: HiHi, Hi, Low, LowLow  
Auto-Reset or Manual Reset 10A SPDT relays 

 

Field scalable Bargraph, does not have to be zero based, 
bargraph can be scaled low-to-high or high-to-low 

 

Scaled 4-20mA output 

 

Color Touchscreen 

 

User entered text for sensor Name, sensor Units, totalizer Units 

 

50 pt Alarm/Event History, Time/Date Stamped 

 

Only 4 7/8” deep, fits in most existing burner control cabinets 

 

Plug-in field wiring terminals 

 

Modbus TCP (Ethernet), Modbus RTU (RS485) 

 

USB port for configuration using free JC_D2Edit PC software 

 

Description 

The

 JC-10D2 

is a field configurable digital Indicator with (2) alarms, 

and flow totalizer (aka Integrator) features. The scaled signal is 
displayed on a backlit color touchscreen LCD display. All 
adjustments can be made directly from the faceplate of the 
instrument by navigating through user friendly menus. JC_Edit PC 
software can also be used to configure the 

JC-10D2

 via the USB port 

and to import the Alarm/Event History into JC_Edit. 

 
 
 
 
 
 

Table of Contents: 

SAFETY .............................................................................. 2

 

Alarm Sequence ................................................................. 2

 

Operation ............................................................................ 3

 

Installation ........................................................................... 4

 

JC-10D2 Indicator Mounting: ......................................... 4

 

Wiring: ............................................................................ 4

 

Menu Map ........................................................................... 6

 

Screen Settings.............................................................. 7

 

Alarms ............................................................................ 7

 

Alarm Types ................................................................... 7

 

Configure / Setup     Analog Input Setup ....................... 7

 

Configure / Setup     mA/Vdc Scaling ............................. 8

 

Configure / Setup     Totalizer Setup .............................. 8

 

Modbus Communications ................................................... 9

 

Parts List .......................................................................... 10

 

Specifications ................................................................... 10

 

Full Size Template ........................................................... 11

 

 
 

Summary of Contents for JC-10D2

Page 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Page 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Page 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Page 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Page 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Page 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Page 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Page 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Page 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...

Page 10: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Page 11: ...SDI JC 10D2 rev 11 17 21 page 11 of 12 Full Size Template 3 61 7 65 Edge of Faceplate outside of panel Mounting Bracket inside of panel JC 30D2 Panel Cutout...

Page 12: ...SDI JC 10D2 rev 11 17 21 page 12 of 12 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...