JC-10D2
Process Bargraph Indicator
with Alarm Relays and Flow Totalizer
Installation & Operation Instructions
JC-10D2 Features
Field selectable Input Signals:
4-20mA, J T/C, K T/C, 10k Thermistor, 0-10V, 0-5V, 0-2.3V
Signal Integrator/Totalizer for Flows, kW, etc with Reset
with Squre Root and Low Flow Cutoff features,
Non-Volitale value storage (no batteries or capacitors)
Configurable Dual Alarms: HiHi, Hi, Low, LowLow
Auto-Reset or Manual Reset 10A SPDT relays
Field scalable Bargraph, does not have to be zero based,
bargraph can be scaled low-to-high or high-to-low
Scaled 4-20mA output
Color Touchscreen
User entered text for sensor Name, sensor Units, totalizer Units
50 pt Alarm/Event History, Time/Date Stamped
Only 4 7/8” deep, fits in most existing burner control cabinets
Plug-in field wiring terminals
Modbus TCP (Ethernet), Modbus RTU (RS485)
USB port for configuration using free JC_D2Edit PC software
Description
The
JC-10D2
is a field configurable digital Indicator with (2) alarms,
and flow totalizer (aka Integrator) features. The scaled signal is
displayed on a backlit color touchscreen LCD display. All
adjustments can be made directly from the faceplate of the
instrument by navigating through user friendly menus. JC_Edit PC
software can also be used to configure the
JC-10D2
via the USB port
and to import the Alarm/Event History into JC_Edit.
Table of Contents:
SAFETY .............................................................................. 2
Alarm Sequence ................................................................. 2
Operation ............................................................................ 3
Installation ........................................................................... 4
JC-10D2 Indicator Mounting: ......................................... 4
Wiring: ............................................................................ 4
Menu Map ........................................................................... 6
Screen Settings.............................................................. 7
Alarms ............................................................................ 7
Alarm Types ................................................................... 7
Configure / Setup Analog Input Setup ....................... 7
Configure / Setup mA/Vdc Scaling ............................. 8
Configure / Setup Totalizer Setup .............................. 8
Modbus Communications ................................................... 9
Parts List .......................................................................... 10
Specifications ................................................................... 10
Full Size Template ........................................................... 11