PD6820 Loop-Powered Process Meter Instruction Manual
8
Open Collector Output
RATING
Isolated open collector, 30 VDC @ 150 mA max.
ALARM OUTPUT
Assign to rate for high or low alarm trip point.
Assign to total for total alarm trip point.
DEADBAND
0-100% FS, user selectable
ACKNOWLEDGE
Front panel ACK button resets output and screen indication.
PULSE OUTPUT
K-FACTOR
K-factor programmable from 0.0001 to 99999. One pulse is
generated for every total increment selected (e.g. K-factor
value of 100 will generate one pulse every time the total is
incremented by 100 units).
If the pulse output exceeds the programmed output fre-
quency, pulses are accumulated as pending and are not
lost. Pulses will continue to output until the buffer is emptied
or the total is reset from the front panel.
PULSE OUTPUT
FREQUENCY
Programmable frequency: 2, 4, 8, 16, 32, 64, 128 Hz.
Minimum pulse width: 3.9 ms @ 128 Hz
Maximum pulse width: 250 ms @ 2 Hz
Factory default pulse width: 31 ms @ 16 Hz