PD6820 Loop-Powered Process Meter Instruction Manual
32
Setting the Tag Display (
tag
)
The meter can be set to display a combination of seven alphanumeric characters for
engineering units (e.g.
GALLONS
) or for identification (e.g.
TANK
3
). Press
Right
arrow
to select next unit and
Up
arrow to increment unit.
To automatically cycle the lower display between total reading for ten seconds
and tag for two seconds, choose
tOgle
.
To disable the tag display and show only total reading uninterrupted on the
lower display, choose
Off.
To show tag only on the lower display choose
On.
Totalizing continues in the
background, but is not shown while
On
is selected.
Selecting
On
or
togle
prompts for entry of the tag.
The unit being changed blinks.
Press the
Enter
button, at any time, to accept a setting or
Menu
button to exit without
saving changes.