ProtEX-MAX PD8-6310-WM Explosion-Proof NTEP Certified Batch Controller Instruction Manual
60
Parameter
Display
Default Setting
Overrange
output
O-rang
21.000 mA
Underrange
output
u-rang
3.000 mA
Loop break
output
break
1.000 mA
Filter
filter
Hi Spd
Cutoff value
CutofF
0.000 (disabled)
Maximum
output
mAx
23.000 mA
Minimum
output
min
1.000 mA
Slave ID
(Address)
Slave Id
247
Baud rate
baud
9600
Transmit
delay
Tr dly
50 ms
Parity
Parity
Even
Byte-to-byte
timeout
t-byt
010 (0.1 sec)
Parameter
Display
Default Setting
F1 function
key
F1
Start
F2 function
key
F2
Preset
F3 function
key
F3
Stop
F4 function
F4
Start/Stop
Digital input 1
dI 1
Menu
Digital input 2
dI 2
Right arrow
Digital input 3
dI 3
Up arrow
Digital input 4
dI 4
Enter
Digital output
1-4
dO 1
Alarm 1-4
Password 1
Pass 1
000000 (unlocked)
Password 2
Pass 2
000000 (unlocked)
Password 3
Pass 3
000000 (unlocked)
Total
password
Total
000000 (unlocked)
Grand total
password
Gtotal
000000 (unlocked)
Troubleshooting Tips
Symptom
Check/Action
SafeTouch buttons do not respond
If mechanical button was pushed. The SafeTouch buttons will
be re-enabled automatically
60 seconds
after the last button
push.
If slide switch on connector board is in DISABLE position,
switch to ENABLE.
Strong direct sunlight may interfere with SafeTouch button
operation. It is recommended to operate the buttons by
standing so as to block direct sunlight.
Serial Communications Power LED
Indicator is off
1. Check modular cable connection
2. Check power to the device
If only the TX (or DATA IN) data
status LED is flashing when serial
communications attempted
1. Check serial cable
2. Check protocol selected on device
3. Check instrument address & baud rate
4. Check program address & baud rate
If both data status LEDs (TX and
RX) are off when trying to
communicate
Remove all unnecessary cables and instruments from the bus.
Try getting the system to work with only one device (to ease
troubleshooting) and then expand the system one device at a
time.
Communications slow
Increase the baud rate
Random communication errors
1. Increase the TX delay time
2. Decrease the baud rate
Power LED is off
1. Check modular cable connection
2. Check power to instrument
No display at all
Check power at power connector
Display reads
LoCd SEAL
when the
Menu button is pressed.
Remove the programming lockout jumper to access
programming menus