ProtEX-MAX PD8-6001 Explosion-Proof Feet & Inches Meter Instruction Manual
5
Ordering Information
SunBright Display Models
85-265 VAC Model 12-24 VDC Model
Options Installed
PD8-6001-6H0
PD8-6001-7H0
No options
PD8-6001-6H7
PD8-6001-7H7
4 relays & 4-20 mA output
*Model number for replacement option card.
WARNING
- Cancer and Reproductive Harm -
Accessories
Model
Description
PDA1232
RS-232 serial adapter
PDA1485
RS-485 serial adapter
PDA7485-I
RS-232 to RS-422/485 isolated converter
PDA8232-N
USB to RS-232 non-isolated converter
PDA8485-I
USB to RS-422/485 isolated converter
PDX6901
Suppressor (snubber): 0.01 µF/470
, 250 VAC
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display
Line 1: 0.60" (15 mm) high, red LEDs
separated by feet and inches
designations
Line 2: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with
lead zero blanking
Display
Intensity
Eight user selectable intensity levels
Display
Update Rate
5/second (200 ms)
Overrange
Display flashes
999999
Underrange
Display flashes
-99999
Display
Assignment
Display lines 1 & 2 may be assigned to
PV1, PV2, PCT, max/min, max & min,
set points, units (line 2 only), or Modbus
input.
Programming
Methods
Four front panel buttons, digital inputs, PC
and MeterView Pro software, or Modbus
registers.
Noise Filter
Programmable from 2 to 199 (0 will
disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of
calibrated span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least
every 12 months.
Max/Min
Display
Max/min readings reached by the
process are stored until reset by the
user or until power to the meter is turned
off.
Password
Three programmable passwords restrict
modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and
editing set/reset points
Pass 3: Restricts all programming, function keys, and
digital inputs.
Power
Options
85-265 VAC 50/60 Hz, 90-265 VDC, 20
W max or 12-24 VDC
10%, 15 W max
Powered over USB for configuration
only.
Isolated
Transmitter
Power Supply
Terminals P+ & P-: 24 VDC
10%.
selectable for 24, 10, or 5 VDC output
supply (internal jumper J4). All models
transmitter supply rated @ 25mA max.
Non-Volatile
Memory
All programmed settings are stored in
non-volatile memory for a minimum of
ten years if power is lost.
Fuse
Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+
supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation
Overvoltage Category III.
Environmental
T6 Class operating temperature range
Ta = -40 to 60°C
T5 Class operating temperature range
Ta = -40 to 65°C