™ PD6001 Analog Input Feet & Inches Meter
Instruction Manual
10
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Line 1: 0.60" (15 mm) high, red LEDs
separated by feet and inches designations
Line 2: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead
zero blanking
Feet & Inches
Range
-9
FT
11
IN
(15/16 or 7/8) to
99
FT
11
IN
(15/16 or 7/8)
Display
Intensity
Eight user selectable intensity levels.
Default value is six.
Display
Update Rate
5/second (200 ms)
LED Status
Indicators
See
Front Panel Buttons and Status LED
on page
Overrange
Display flashes
999999
Underrange
Display flashes
-99999
Display
Assignment
Display Line 1:
PV1, max/min, max & min, set points, or
Modbus input.
Display Line 2:
Same as Display Line 1; plus units, tag,
PV2, percent of PV1, PV1 level in feet &
unit/tag, or turned off.
Programming
Methods
Four front panel buttons, digital inputs, PC
and MeterView Pro software, or Modbus
registers.
Noise Filter
Programmable from 2 to 199
(0 will disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of
calibrated span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least
every 12 months.
Max/Min
Display
Max/min readings reached by the process are
stored until reset by the user or until power to
the meter is turned off.
Rounding
Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10,
actual value = 12.093,
secondary display = 12.090,
main display = 12
FT
1
IN
1
/
16
).
Password
Three programmable passwords restrict
modification of programmed settings.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Non-Volatile
Memory
All programmed settings are stored in non-
volatile memory for a minimum of ten years
if power is lost.
Fuse
Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
Operating temperature range:
-40 to 65°C (-40 to 149°F)
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
0 to 90% non-condensing
Connections
Removable screw terminal blocks accept
12 to 22 AWG wire, RJ45 for external
relays, digital I/O, and serial communication
adapters.
Enclosure
1/8 DIN, high impact plastic, UL 94V-0,
color: black
Front Panel
NEMA 4X, IP65
Mounting
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies
are provided.
Tightening
Torque
Screw terminal connectors: 5 lb-in
(0.56 Nm)
Overall
Dimensions
4.68" x 2.45" x 5.64"
(119 mm x 62 mm x 143 mm)
(W x H x D)
Weight
9.5 oz (269 g)
Warranty
3 years parts & labor. See Warranty
Information and Terms & Conditions on