ProtEX-MAX PD8-6210 Explosion-Proof Analog Input Batch Controller
Instruction Manual
59
Advanced Setup &
Programming
In addition to the functions described in
, the following advanced
operation and display features may be programmed.
Please note that configuring these features may
disable some default batch controller features or it
can make running a batch operation impossible.
These functions should only be used by users who
are sure of their need in their application.
Advanced Features Menu
To simplify the setup process, functions not needed
for most applications are located in the
Advanced
Features
menu.
Press and hold the Menu button for three seconds to
access the advanced features of the controller. This
cannot be done during a batch process as all
functions other than STOP are disabled during a
batch process, including the Menu button.
Advanced Features Menu &
Display Messages
The following table shows the functions and
messages of the
Advanced Features
menu in the
order they appear in the menu.
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
filter
Filter
Set noise filter value
bypASs
Bypass
Set filter bypass value
Round
Round
Set the rounding value for
display variables
seriAl
Serial
Set serial communication
parameters
SlaVId
Slave ID
Set slave ID or controller
address
baud
Baud rate
Select baud rate
Tr dLY
Transmit
delay
Set transmit delay for serial
communication
Parity
Parity
Select parity Even, Odd, or
None with 1 or 2 stop bits
t-byt
Time byte
Set byte-to-byte timeout
Advanced Features Menu & Display Messages
Display
Parameter
Action/Setting
SelEct
Select
Enter the Select menu
(function, cutoff, out)
Functn
Input Signal
Conditioning
Select linear, square root,
or programmable exponent
Linear
Linear
Set controller for linear
function and select number
of linearization points
No PtS
Number of
points
Set controller for 2 to
32-point linearization
Square
Square root
Set controller for square
root extraction
Prog E
Programmable
exponent
Set controller for
programmable exponent
and enter exponent value
CutofF
Cutoff
Set low-flow cutoff
Count
Count
Set the totals to count up
or down from a set value
Tot C
Total count
Set the batch to count up
to or down from the preset
up
Up
Set the total to count up
Douwn
Down
Set the total to count down
Gtot C
Grand total
count
Set the grand total to count
up or down from a defined
value
C strt
Count start
Set the starting grand total
value when counting down
AoutPr
Analog output
programming
Program analog output
parameters
Source
Source
Select source for the
4-20 mA output
O-rang
Overrange
Program mA output for
display overrange
u-rang
Underrange
Program mA output for
display underrange
Break
Loop Break
Set analog output value if
input loop break is
detected
Force
Force output
Force analog output value
for loop break
Ignore
Ignore
Ignore loop break condition
nmAx
Maximum
Program maximum mA
output allowed
nmin
Minimum
Program minimum mA
output allowed
Calib
Calibrate
Calibrate 4-20 mA output
(internal reference source
used for scaling the output)
4 nmA
4 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
20 nmA
20 mA output
Enter mA output value
read by milliamp meter
with at least 0.001 mA
resolution
user
User I/O
Assign function keys and
digital I/O