ProtEX-MAX PD8-6100 Strain Gauge, Load Cell, and mV Meter
Instruction Manual
30
Setup and Programming
There is
no need to recalibrate
the meter when first received from the factory, if
used to read millivolts.
The meter is
factory calibrated
prior to shipment for millivolts with calibration
equipment that is certified to NIST standards.
If the meter is used with a strain gauge or load cell, it is recommended to perform a
live calibration with the sensor connected.
Overview
There is a 5-position DIP switch on the back of the control module to set the meter input selection. See
Setup and programming is done using MeterView Pro or through the programming buttons.
After power and input signal connections have been completed and verified, apply power to the meter.
LED Status Indicators
LED
State
Indication
1-4
Steady
Alarm condition based on set and reset points, independent of relay
status in certain configurations. (Available on all meter
configurations, including those without relays installed)
1-4
Flashing
Relay interlock switch open
1-4 & M
Flashing
Relay in manual control mode
T
Flashing
Meter in Tare mode
M
Flashing
Analog output in manual control mode
G
Steady
Gross value being displayed