PD6928 Ex-Proof & I.S. Loop-Powered Flow Rate/Totalizer
Instruction Manual
70
Function Keys Operation
During operation, the programmable function keys
operate according to the way they have been
programmed in the
Advanced Features
– User
menu.
The table under
shows the factory default settings for F1, F2,
and F3.
A hint message may be enabled to provide a
description of what each function key does prior to
executing their assigned function. See
) on page
Digital Input Operation
A digital input is standard on the meter. This digital
input is programmed identically to function keys F1,
F2, and F3. The input is triggered with a contact
closure between DI+ and DI-, or with an active low
signal. During operation, the digital input operates
according to the way it has been programmed in the
Advanced Features
– User
menu. Factory default
setting is to reset total.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by
the process can be displayed either continuously or
momentarily.
Display momentarily by pressing the F1 function key
(default) or assigning to any of the other function keys
or to the digital input in the
User
menu.
Display continuously by pressing the
Enter
button
while the max/min is being displayed to lock the
display. Press
Enter
again to unlock.
Any of the F1-F3 function keys (buttons) and the
digital input can be programmed to reset the max &
min readings. The meters are set at the factory to
display the max reading by pressing the
Right
Arrow/F1
button and to use the
Up-Arrow/F2
button to
access the
Reset
menu. Press the
Right Arrow
button
to cycle through the available parameters to reset.
Top Display:
Process Value
Bottom Display:
Max & Min
Total Reset Capabilities
The total and grand total can be reset using a
CapTouch button, an external contact closure on the
digital input, or MeterView XL software. In addition,
both total and grand total reset can be password
protected to prevent unauthorized resets.
Total Reset via CapTouch Button
The CapTouch function key F2 is set up to reset the
total. If reset grand total is enabled, it is possible for the
user to reset either the total or the grand total without
removing the cover or the need for external devices.
Total Reset via Digital Input
The PD6928’s digital input can also be used to reset the
total or grand total.
Total Reset Password Protection
Total and grand total passwords can be set to prevent
resetting the total or grand total unless a password is
entered. Grand total reset can be disabled through
the meter interface, and it can also be permanently
disabled. See
Non-Resettable Grand Total
The user can set up the grand total to be non-resettable by
selecting
YES
at the
PERMLOC
menu; see page 62 for
details. Once this is done, the grand total can never be reset.
- +
DI