PD6600 Series Loop-Powered Process Meters
Instruction Manual
27
Main Menu
The main menu consists of all the meter’s programma-
ble functions:
Input
,
Output, Advanced,
and
Display
.
•
Press
Menu
button to enter
Programming Mode
then press the
Right-Arrow
button to move for-
ward through the menu and the
Up-Arrow
button
to move back.
•
Press
Menu
at any time to go back one level or
press & hold to exit and return to
Run Mode
.
Changes made to settings prior to pressing
Enter
are not saved.
•
Changes to the settings are saved to memory
only after pressing
Enter/F3
to confirm the set-
ting or pressing
Enter/F3
at the
SAVE?
screen
when available.
Note:
The
BARGRAPH
menu appears in the PD6604/8
menu only.
Setting Numeric Values
The numeric values are set using the
Right
and
Up-Arrow
buttons.
1. Press
Right-Arrow
to select next digit and
Up-Arrow
to increment digit value. The
selected digit will flash.
2. Press and hold
Up-Arrow
to auto-increment
the display value. If you have made a
mistake or would like to enter a new value,
select the left-most digit, and press and hold
the
Right-Arrow
button until all digits reset
to zero.
3. Press the
Enter
button at any time to accept
a setting or
Menu
button to exit without
saving changes.
Note:
the underscore in the graphic below is provided
to show which digit would be flashing.
Scaling the 4-20 mA Input (
INPUT
)
It is
very important
to read the following information
before proceeding to program the meter:
•
The meter is factory calibrated prior to shipment
to display 0.00 to 100.00 gal, which corresponds
to the 4-20 mA input. The calibration equipment
is traceable to NIST standards.
•
A calibrated signal source is not needed to scale
the meter.
Enter the
Input
menu to scale the meter to display the
4-20 mA input. The input can accept any signal from
4 to 20 mA.
52.86
GAL
SETUP
INPUT
SETUP
OUTPUT
SETUP
ADVANCED
SETUP
DISPLAY
OPEN
COLLECTR
ADV
PV SETUP
DSPLY
UNITS
OUT
RELAY
OUT
4-20 mA
OUT
CONTROL
CUTOFF
FILTER
PASSWRD
USER
SYSTEM
DSPLY
DEC.PT
DSPLY
COMMA
DSPLY
TOP
DSPLY
BOTTOM
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP
1
SCALE
INPUT 2
SCALE
DISP
2
DSPLY
BARGRAPH
*PD6604/8
Only
*
Run Mode
SETUP
INPUT
DSP 1
+00,000.00
DSP 1
00,000.00
Select
Digit to
Change
DSP 1
00,050.00
Increment
Selected
Digit
SCALE
INPUT 2
Accept
Setting
SETUP
INPUT
SCALE
UNITS
SCALE
INPUT 1
SCALE
DISP 1
UNITS
VOLUME
HEIGHT
TEMP
PRESSURE
WEIGHT
RATE
CUSTOM
UNIT
GAL
GAL
L
IGAL
M3
BBL
BUSH
cuYD
cuFt
cuIn
LiBBL
BBBL
HECtL
AF
CUSTOM
INCH
FEET
FT-IN
YARD
CM
M
CUSTOM
~F
~C
K
~RA
PSI
InHg
InH2O
mmHg
kg/CM2
kg/M2
mBAr
Bar
PA
hPA
kPA
MPA
CUSTOM
gm
kg
tonne
oz
1b
ton
CUSTOM
/SECOND
/MINUTE
/HOUR
/DAY
GAL/
(T)
L/
(T)
IGAL/
(T)
M3/
(T)
BBL/
(T)
BUSH/
(T)
cuYD/
(T)
cuFt/
(T)
cuIn/
(T)
LiBBL/
(T)
BBBL/
(T)
HECtL/
(T)
AF/
(T)
CUSTOM/
Volume Units
Height Units
Pressure Units
Weight Units
Rate Time
Bases
Rate Units
Temperature
Units
INP 1
04.000
INP 1
mA
Flashes Units
Momentarily
DSP 1
+00,000.00
SCALE
INPUT 2
INP 2
20.000
SCALE
DISP 2
DSP 2
+00,100.00
SAVE?
SETUP