PD6600 Series Loop-Powered Process Meters
Instruction Manual
15
I.S. Equipment
Entity
Parameters
Required
Relationship
Between Entity
Parameters
I.S. Barrier Entity
Parameters
V max (or Ui)
≥
Voc or Vt (or Uo)
I max (or Ii)
≥
Isc or It (or Io)
P max, Pi
≥
Po
Ci + Ccable
≤
Ca (or Co)
Li + Lcable
≤
La (or Lo)
•
For Division 2 and Zone 2 Applications:
Division 2 and Zone 2 installations do NOT require
the use of an intrinsically safe barrier or
intrinsically safe entity parameters. Class I,
Division 2, Groups A, B, C, and D T4 and Class I,
Zone 2, Group IIC T4, -40C <= Ta <= +70C.
Ratings: V = 30 V dc, I = 30 mA; Relay Ratings:
250V ac/dc 1A
For North American Community:
Installation and service of this device and/or
associated apparatus (barrier) should be performed
only by trained service personnel
and must be installed in accordance with the
manufacturer’s control drawing, Article 504 of the
National Electric Code (ANSI/NFPA 70) for installation
in the United States, or Section 18 of the Canadian
Electrical Code for installations in Canada.
•
EXPLOSION HAZARD
– Do not disconnect
equipment unless power has been removed or
the area is known to be non-hazardous.
•
RISQUE D’EXPLOSION
– NE PAS BRANCHER
NI DÉBRANCHER SOUS TENSION.
Year of Construction
This information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
EU Declaration of Conformity
EU Declaration of Conformity for the PD6602/04 and
PD6606/08 are available in the Documentation CD
provided with the product under the
EU DoC
menu.
Safety Information
•
Read complete instructions prior to installation
and operation of the meter.
•
Hazardous voltages exist within enclosure.
Installation and service should be performed only
by trained service personnel.
•
Service requiring replacement of internal
components must be performed at the factory.
•
Control room equipment must not use or
generate more than 250 VRMS or VDC.
•
Hazardous location installation instructions for
associated apparatus (barrier) must be followed
when installing this equipment.
•
For safe installation of an ATEX approved
transmitter in series with PD6606/PD6608 loop-
powered meters, the hazardous location
installation instructions for the transmitter,
PD6606/PD6608 loop-powered meter, and
associated apparatus (barrier) must be
compatible.
•
PD6606/PD6608 Series Loop-Powered meters
do not add capacitance or inductance to the loop
under normal or fault conditions.
•
Substitution of components may impair
hazardous location safety.
•
Equipment contains non-metallic materials and
therefore special care and consideration should
be made to the performance of these materials
with respect to chemicals which may be present
in a hazardous environment.