6334V105
19
Cold junction compensation ....................... < ±1.0°C
Sensor error detection ................................ Yes
Sensor error current:
When detecting .................................... Nom. 33 mA
Else....................................................... 0 mA
voltage inputs:
Measurement range .................................... -12...150 mV
Min. span ..................................................... 5 mV
Input resistance ........................................... 10 M
Ω
Outputs:
Current outputs:
Signal range ................................................ 4...20 mA
Min. signal range ......................................... 16 mA
Updating time .............................................. 440 ms
Output signal at EEprom error ....................
≤
3.5 mA
Load resistance ...........................................
≤
(V
supply
- 7.2) / 0.023 [
Ω
]
Load stability ............................................... < ±0.01% of span / 100
Ω
Sensor error detection:
Programmable ............................................. 3.5...23 mA
Namur NE43 Upscale .................................. 23 mA
Namur NE43 Downscale ............................. 3.5 mA
Of span = Of the presently selected range