26
9203 - Product Version 9203-001
Fm Installation Drawing
9203QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2009-12-10
Version Revision
V3 R0
Prepared by:
PB
Page:
1/2
FM Installation drawing
9203
For safe installation of 9203B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
c-FM-us Certificate 3035277
Non Hazardous Area or
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
-20
≤
Ta
≤
60ºC
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9203
4501
Power
Rail
91 92 93 94 95
Supply / Input
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V, max. 400 Hz
Hazardous area
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui)
≥
Vt (Uo)
Imax (Ii)
≥
It (Io)
Pi
≥
Pt(Po)
Ca(Co)
≥
C
cable
+ Ci
La(Lo)
≥
L
cable
+ Li
CONTENTS