IECEx Installation drawing
9203
For safe installation of 9203B the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
Certificate
IECEx KEM 09.0001X
Marking
Standards
IEC60079-15:2005, IEC60079-11:2006, IEC60079-0:2007
IEC60079-26:2006, IEC61241-0:2004, IEC61241-11:2005
Hazardous area
Non Hazardous area
Zone 0, 1, 2, 20, 21, 22
or Zone 2
Ex nA nC IIC T4 Gc
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
Supply / Input
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V, max. 400 Hz
-20
≤
Ta
≤
60ºC
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9203
4501
Power
Rail
91 92 93 94 95