16
9203 - Product Version 9203-001
Signal error indications without display front
cONFIgURATION /
OPERATINg ThE FUNcTION KEYS
Documentation for routing diagram.
In general
When configuring the 9203, you will be guided through all parameters and you
can choose the settings which fit the application. For each menu there is a
scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
1
will increase the numerical value or choose the next parameter
2
will decrease the numerical value or choose the previous parameter
3
will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding
3
will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
LED and error signal indications
State
green LED
ch 1:
Yellow / Red
ch 2:
Yellow / Red
Status relay,
N.c.
Power rail
signal status
Device OK
Flashing
Energised
OFF
No supply
OFF
OFF
OFF
De-energised
ON
Device defective
OFF
Red
Red
De-energised
ON
Ch. 1, output ON
Flashing
Yellow
Energised
OFF
Ch. 1, output OFF
Flashing
OFF
Energised
OFF
Ch. 2, output ON
Flashing
Yellow
Energised
OFF
Ch. 2, output OFF
Flashing
OFF
Energised
OFF
CONTENTS