CONTROl DRAWING 5107QU01
Hazardous (Classified) location
Class I, Division 1, Group A,B,C,D
Class I , Zone 0 and 1, Group IIC
Class II, Division 1 Group E, F, G
Intrinsically safe apparatus
entity parameters:
Vmax. (Ui)
≥
Voc (Uo)
Imax. (Ii)
≥
Isc (Io)
Pi
≥
Po
Ca
≥
Ci
La
≥
Lcable + Li
The sum of capacitance and inductance
of cable and intrinsic safe equipment
must be less or equal to Ca and La
Installation notes:
1) The maximum nonhazardous location voltage is 250 VAC/DC.
2) The installation shall be in accordance with the National Electrical Code
NFPA 70, Articles 504 and 505.
3) The terminals of the two individual channels shall not be interconnected in any
way.
4) Install in Pollution degree 2 or better
5) Use 60 / 75 °C copper conductors with wire size AWG: (26 – 14).
6) Warning: Substitution of components may impair intrinsic safety.
5107B Associated apparatus parameters
CH1
Terminals 41 to 43
CH2
Terminals 51 to 53
Voc (Uo)
28 V
Isc (Io)
93 mA
Po
0.65 W
IIC / grp. A,B IIB / grp. C IIA / grp.D
Ca (Co)
0.06
μ
F
0.52
μ
F
1.72
μ
F
La (Lo)
2.4 mH
12 mH
20 mH
Nonhazardous
Associated apparatus
Galvanically isolated
Rev. AA 2003-01-22
Summary of Contents for Hart 5107B
Page 10: ...8 I P mA I P Konverter Strøm mA Indgang Indgang Forsyning Forsyning Applikationer ...
Page 16: ...14 ...
Page 24: ...22 I P mA Input Input Supply Supply Current mA I P Converter Applications ...
Page 30: ...28 ...
Page 38: ...36 I P mA Alimen Courant mA Alimen Convertisseur I P Entrée Entrée Applications ...
Page 44: ...42 ...
Page 52: ...50 I P mA Versorgung Versorgung Strom mA I P Konverter Eingang Eingang Anwendungen ...
Page 58: ...56 ...