FM Installation drawing
For safe installation of 9107B the following must be observed. The module shall only be
Installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
9107BA:
1 channel
HART
-transparent driver
9107BB:
2 channel
HART
-transparent driver
Installation notes:
In Class I, Division 2 installations, the subject equipment shall be mounted within a too-secured enclosure
which is capable of accepting one or more of the Class I, Division 2 wiring methods specified in the National
Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1).
In Class I, Zone 2 installations, the subject equipment shall be mounted within a tool secured enclosure which
is capable of accepting one or more of the Class I, Zone 2 wiring methods specified in the National Electrical
Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1). Where installed in outdoor or potentially wet
locations, the enclosure shall, at a minimum, meet the requirements of IP54.
Install in environments rated Pollution Degree 2 or better; overvoltage category I or II.
The equipment shall be installed in an enclosure with a minimum ingress protection rating of IP54 unless the
apparatus is intended to be afforded an equivalent degree of protection by location.
The module is galvanically isolated and does not require grounding.
Use 60 / 75 ºC copper conductors with wire size AWG: (26-14)
Warning
: Substitution of components may impair intrinsic safety.
Status Relay. terminal (33,34)
Voltage max:
125VAC / 110VDC
Power max:
62,5VA / 32W
Current max:
0.5A AC / 0.3ADC
Zone 2 installation:
Voltage max:
32VAC / 32VDC
Power max:
16VA / 32W
Current max:
0.5A AC / 1ADC
Supply terminal (31,32)
Voltage:
19.2 – 31.2 VDC
FM Installation Drawing
9107 - Product version 9107-002
25