![PQ Plus CMD 68-104 Quick Start Manual Download Page 3](http://html.mh-extra.com/html/pq-plus/cmd-68-104/cmd-68-104_quick-start-manual_1592841003.webp)
PQ Plus – CMD 68-54/104 V2
3
EN
Installation
Direct connection
Current (I
st
, I
min
, I
tr
, I
ref
, I
max
)
0.02 A / 0.15 A / 0.5 A / 5 A / 100 A
Current transformer /5 und /1A
Current /5A
(I
st
, I
min
, I
tr
, I
ref
, I
max
)
0.005 A / 0.05 A / 0.25 A / 5 A / 5 A
Current /1A
(I
st
, I
min
, I
tr
, I
ref
, I
max
)
0.002 A / 0.01 A / 0.05 A / 1 A / 1 A
Installation instruction
Torque Connection
Flexible wire
Direct
max. 25mm
2
strand
Current transformer
max. 6mm
2
strand
Input lead L1/L2/L3
2-3 Nm
1.3 - 1.6 Nm
Neutral conductor
2-3 Nm
1.3 - 1.6 Nm
S0 pulse output Cage clamp up to max 2.5mm
2
strand
Tariff control
Cage clamp up to max 2.5mm
2