Set the System Data & Time
Navigation:
MENU SET CLOCK
1. Press in a white box to
change values.
Format:
MONTH/DAY/YEAR | MINUTE: SECOND
2. A keypad will appear—use it to input the new password:
a. ENT – accepts the value.
b. CLR – clears numbers on display.
c. CAN – return to previous screen.
NOTE: All white fields need to have updated numbers before
pressing update. Even if they are correct.
Control Panel Temperature Settings
Navigation:
MAIN/MENU
PANEL TEMP SETTINGS
SETTING
DEFINITION
Low Temp
Alarm Limit
High Temp
Alarm Limit
System alarms when the control panel reaches
this temperature.
System alarms when the control panel reaches
this temperature.
8.8 Additional Automation Functions
8.9 Control & Monitoring by Others
Line Fill Mode
Master Valve Settings
Navigation:
MENU LINE FILL MODE
Navigation:
MENU MASTER VALVE
SETTING
SETTING
DEFINITION
DEFINITION
Enable/
Disable
OPERATION
STEP PSI
STEP DELAY
ENABLED: Line fill mode will begin automati-
cally the next time that the system is started.
DISABLED: Line fill mode disabled.
The controller increases the PSI Setpoint by
this value after each Step Delay time has
passed.
How long the controller maintains the PSI Set-
point before increasing it by the Step PSI value.
TEST: Valve is energized to close.
AUTO: Valve automatically opens and closes.
OFF: Valve remains Open.
About Line Fill Mode
When pumping into an empty or non-pressurized pipe network,
it’s important to fill it slowly—otherwise, pumping at full speed
can cause pressure surges or water hammer, which can severely
damage the piping network.
In Fill Mode, the system gradually fills and pressurizes the piping
network:
1. The controller raises the PSI Setpoint in increments entered in
the Step PSI parameter.
2. The pump system brings up and maintains the PSI Setpoint for
the Step Delay time.
3. After the Step Delay time has passed, the process is repeated.
This occurs until the pressure setpoint is reached.
About Master Valve
The Master Valve is designed to
open and close electronically when
it receives a signal from the VFD.
NOTE: Control and Monitoring of this station was provided by
others and is outside the scope of this manual.