Adjust the Discharge Pressure Setpoint
Intake PID Mode
Adjust Intake Pressure Fault Settings
Adjust the Discharge Pressure Fault Setpoint
Navigation:
MAIN PRESSURE
Navigation:
MAIN INTAKE
PRESSURE INTAKE
PID MODE
Navigation:
MAIN INTAKE PSI
Navigation:
MAIN PRESSURE
SETTING
SETTING
SETTING
SETTING
DEFINITION
DEFINITION
DEFINITION
DEFINITION
PSI Setpoint
Actual Setpoint
Current Pressure
0% Setpoint
Intake PSI
100% Setpoint
Intake PSI
Intake PID
Filter Delay
LOW INTAKE
ALARM LIMIT
DELAY
Restart Trials
Restart Delay
ALARM LIMIT
DELAY
Discharge pressure that the system is
set to automatically maintain.
Displays the pressure setpoint as
manipulated a PID mode.
1- Intake PID Mode. System
automatically adjusts the PSI
Setpoint to prevent intake pressure
from dropping too low.
2- Level PID mode. System
automatically adjusts the PSI
Setpoint to prevent water level
from dropping too low.
Displays the current discharge pressure.
The minimum intake pressure value
that the system
The maximum intake pressure value
that the system uses to calculate the
system setpoint.
If the intake pressure is at or above the
100% setpoint, the system setpoint is
not manipulated by PID mode.
How often the PID mode system
samples the intake pressure
measurements.
System faults when the intake pressure
reaches this value below the PSI Setpoint.
Time between fault parameter detection
and system shut down.
How many times the system attempts to
restart after a fault occurs.
Time between restart trials.
High Pressure. System faults when the
pressure reaches this value above the
PSI Setpoint.
Low Pressure. System faults when the
pressure reaches this value below the
PSI Setpoint.
Time between fault parameter
detection and system shut-down.
About Pressure Fault
Settings: To prevent
damage to the system, the
controller will shut-down
the station if the pressure is
too high, or too low.
About Intake PID Mode:
When in this mode, the station
varies the system setpoint
based on the available intake pressure. It bases this on a range of
intake pressure values. This range is limited to values entered in the
0% Setpoint Intake PSI and 100% Setpoint Intake PSI fields.
About Pressure
Fault Settings:
To prevent damage to the
system, the controller will
shut down the station if the
intake pressure is too low.
8.1 Pressure Settings