Chapter 8 RS485 communication
Powtran PR5200 series soft starter with built-in RS485 standard interface which can be
communicated with the PC and PLC host .
It Can be controlled by the host command of soft starter run/stop, monitoring the running state
of soft starter and modify its function data, and so on.
8-1.Summary of the modbus RTU communication protocol
Modbus is a kind of serial asynchronous communication protocol. The physical interface
RS485.Modbus is designed to modicon PLC, has the structure characteristic of PLC. Modbus in
network control, the soft starter can be compared to a PLC to read and write on it. Start-stop
control and status information (current, fault, etc.) And the function parameter mapping to keep
register area
8-1-1.Communication parameters
Baud rate:9600
;
8 Data bits
;
No parity bit
;
1 stop bit.
8-1-2.Communication data format
The data format:
Address code
Function code
Data area
CRC check
1 byte
1 byte
N byte
2 byte
8-2.The soft starter associated settings
8-2-1.Register address
Register address
Operation code
Register function description
0001
06
Control word
0002
03
Status word
0003
03
The average current
0004
03
Fault code
0256-0274
03&06
Soft starter function code
Register is not listed above is illegal, cannot read and write, otherwise it will report to the
controller an exceptional code from the station.
8-2-2.Support code
Soft start only supports the following code, if you use other code, will give exceptions to the
code.
Code
03
06
Function description
Read the register
Write a single register
Code 03 only WORD (WORD) to read.
8-2-3.The register description
0001 The command register
Digit
Value
0
1
Starter starting
0
Keep the mold
1
1
Starter stop
0
Keep the mold
Summary of Contents for PR5200 Series