5-2 Function parameters setting and description
Function parameters code in the following table
Code Setting Description
Code
Name
Range of
set value
Factory
setting
Explanation
P0
Starting voltage
30-70%
30%
Voltage slope model is effective, the starting
voltage of current mode is 40%.
P1
Soft starting time
2-60S
16S
Limiting current mode does not work.
P2
Soft stop time
0-60S
0S
Setting 0 means free stopping, please set 0 for
one with two onnections .
P3
Start interval delay
0-999S
0S
The minimum time between two successive
start, the function of protecting thyristor.
P4
Language selection
0 or 1
0
0 for Chinese display, 1 for the English
display.
P5
Starting current limit
50-400%
280%
The current limiting mode is effective; the
maximum flow value of the voltage slope
mode is 400%.
P6
Load regulation rate
50-200%
100% Relative to the value of the rated current PP.
P7
Under voltage
protection
40-90%
80%
Protection below the set value.
P8
Overvoltage protection 100-140%
120% Protection is higher than the set value.
P9
Starting mode
0-6
1
0 limit current; 1 voltage; 2 jump; limit
current; 3 jump + voltage; 4 current ramp; 5
double closed loop; 6 monitoring.
PA Protection level
0-4
4
0 primary; 1 light load; 2 standard; 3 heavy
load; 4 advanced.
PB Control mode
0-6
1
0 keyboard; 1 ke external control; 2
external control; 3 external c
communication; 4 ke external control
+ communication; 5 ke
communication; 6 communication.
PC
Parameter
modification allowed
0-3
1
See 5.5 other setup instructions.
PD
Correspondence
address
0-64
0
For MODBUS native slave address setting.
PE Programming output
0-19
7
See 5.3 programmable relay output functions.
PF Soft stop current
20-100%
80%
See 7.3.1 soft stop mode.
PP Motor rated current
11-998A
Rated
value
Nominal rated current for input motor.