Powrmatic NVx Series User, Installation And Servicing Instructions Download Page 17

NVX Range  Users, Instructions & Service Instructions Issue 5.5 August 2015                                                                                  Page 17

2.1.1 Fitting space requirement

For NVx/D units the normal air flow direction is from right 

to left when viewing the heater from the burner/controls 

end with the fan unit upstream.

The minimum clearances must be observed for installa-

tion and servicing.

All models must not be installed at a height of less than 

2.5m to the base of the unit.

Any combustible material adjacent to the air heater and 

the flue system must be so placed or shielded as to 

ensure that its temperature does not exceed 65 °C.

When NVx modular components are used in conjunction 

with the heater each component must be individually 

supported.

Note: The access door to the controls section 

may be removed to improve access. Open the 

door to 90°, remove the earth cable at the bottom, 

and then lift the door vertically upwards to disen-

gage the hinge plates. Refit in reverse order. 

Ensure that the earth cable is refitted. 

The air heater may be installed either:

a) suspended from suitable vertical drop rods.

b) on specifically designed cantilever brackets from a non 

combustible wall.

c) on a level noncombustible surface. The surface must 

not extend past the front edge of NVx/F heaters.

The method of installation must be capable of adequately 

supporting the weight of the unit (See Table 3, Page 30) 

and any ancillary equipment. Before installing the heater 

the existing structure must be inspected to ensure it is 

suitable. All supports should be protected against the 

effects of rust or corrosion. 

Raise the heater up to the point of installation using 

suitable and safe means and connect to the means of 

suspension. 

Note: Each heater is provided with additional 

central suspension points (suspension points 

running along the front and back are for perma-

nent connection, suspension points running left to 

right in the centre are for temparary support) that 

can be used to provide temporary support, using 

suitable means, whilst the unit is being installed. 

Under no circumstances must these points be 

used as the final means of suspension.

2.1.2 Suspending the heater 

Threaded drop rods must have lock nuts fitted that are 

tightened down onto the 10mm fixings in the heater. If 

reducing noise levels is important the heater should be 

insulated from the structure by installing it on suitable 

anti-vibration mountings. In all such cases and when the 

heater is suspended it is essential that all gas, duct, and 

electrical connections to the heater are made with flexible 

connections to maintain continuity of connection.

2.1.3 Air Distribution System
2.1.3.1 General

NVx/D and NVx/C models are designed for use with duct 

work to more precisely define the point of air delivery, and 

/or provide ducted return air or ducted fresh air inlet. All 

ducting must be independently supported of the air 

heater.

Joints and seams of supply ducts and joints between NVx 

ancillary components must be securely fastened and 

made airtight using appropriate sealants or sealing strips. 

If required the duct work should be insulated to reduce 

heat loss.

2.1.3.2 Noise Reduction

Ducting should be connected to the heater spigots via an 

airtight flexible coupling of noncombustible material. 

Before fitting the coupling it must be ensured that a 

minimum clearance of approximately 15mm will be main-

tained between the ends of the ducting and the heater 

spigots. 

Sound attenuators may be fitted in inlet and outlet ducts to 

reduce airborne fan noise. Materials used in outlet sound 

attenuators must be capable of withstanding 100°C air 

temperature without any deterioration.

2.1.4 Room Thermostat Siting

The room thermostat should be fitted at a point which will 

be generally representative of the heated area as far as 

temperature is concerned. Draughty areas, areas subject-

ed to direct heat e.g. from the sun, and areas where the 

air movement is relatively stagnant e.g. in recesses, 

should be avoided. The thermostat should be mounted 

approximately 1.5m from the floor.

Any room thermostat, frost thermostat, time clock etc. 

must be suitable for switching 230V, 5A and must be of 

the 'snap action' type to minimise contact bounce.

For electrical connections of external controls see the 

accompanying wiring diagram.

2.6.6.1. Standard Units

This is set for the required heat input before despatch. In 

the case of Hi/Lo and Modulating units both high and low 

pressures are set. Pressures should be checked in the 

following manner.

2.6.6.1.1. Standard Units

1. Set external controls to ensure that the main burner is 

off.

Open the side access door. Connect a pressure gauge to 

the burner pressure test point on the multifunctional 

control.

2. Set external controls so as to turn on the main burner. 

Compare the measured burner gas pressure to that 

stated on the data plate. If necessary adjust the burner 

gas pressure by turning the regulator screw anticlockwise 

to decrease the pressure, or clockwise to increase the 

pressure. 

3. In addition it is advisable to check the gas rate using the 

gas meter dial pointer. Ensure that no other appliances 

supplied through the meter are in operation.

4. If required, after checking or setting the burner pres-

sures, the CO2 content in the flue gases can be checked 

by sampling in the first section of flue fitted to the flue 

outlet of the unit. Nominal CO2 values are given for guid-

ance in the Table at the bottom of the previous page.

5. Turn off the main burner and disconnect the pressure 

gauge and replace the sealing screw. Turn on the main 

burner as above and test for gas soundness around pres-

sure test joint using a leak detection fluid e.g. soap 

solution.

Governor adjustment screw under cover cap (Honeywell 

VK4105A1001B) 

Fitted to the NVx 10 to 50

Governor adjustment screw under cover cap

 (Honeywell VR4605AB1027)

 

Fitted to the NVx 60, 75, 90 and 90S

Governor adjustment screw under cover cap (Honeywell 

VK425AB1007)

 

Fitted to the NVx 120 and 140

2.6.6.1.2. High/Lo Regulator

1. Set external controls to ensure the main burner is off. 

Open the side access panel. Connect a pressure gauge to 

the burner pressure test point on the multifunctional 

control.

2. Set external controls to turn on the main burner and 

maintain high fire. Compare the measured burner gas 

pressure to that stated on the data plate. In addition it 

is advisable to check the gas rate using the gas meter dial 

pointer ensuring that no other appliances supplied 

through the meter are in operation.

3. Repeat 2 above with external controls set to maintain 

low fire.

4. If it is necessary to adjust either the high fire or low fire 

pressures proceed as follows after levering off the plastic 

cover from the Hi/Lo regulator.

Note: High fire setting must be adjusted first after 

which the low fire setting can be set. Any adjust-

ment of the high fire setting alters the minimum 

setting.

Maximum Setting

With the controls set to high fire use an adjustable or 8mm 

spanner to turn the adjustment screw for high fire pres-

sure, clockwise to increase and counter-clockwise to 

decrease, until the required pressure is obtained. Turn the 

burner On and OFF several times to check the pressure 

setting and then turn off.

Minimum Setting

Disconnect electrical connection of high/low regulator and 

turn burners back on and wait until the burner pressure 

has stabilized. Use a screwdriver to turn the slotted 

adjustment screw for low fire pressure, clockwise to 

increase and counter-clockwise to decrease, until the 

required pressure is obtained. Reconnect high/low regu-

lator and check high fire pressure. Repeat both steps if 

necessary and then replace cover cap. 

5. Turn off the main burner, disconnect the pressure 

gauge and replace the sealing screw. Turn on the main 

burner and test for gas soundness around pressure test 

joint using a leak detection fluid. Replace access panel.

2.6.6.1.3. Modulating Regulator

1. Set external controls to ensure that the main burner is 

off. Open the side access panel. Connect a pressure 

gauge to the burner pressure test point on the multifunc-

tional control. 

2. Set external controls so as to turn on the main burner 

and maintain high fire. Compare the measured burner gas 

pressure to that stated on the data plate. In addition it is 

advisable to check the gas rate using the gas meter dial 

pointer ensuring that no other appliances supplied 

through the meter are in operation. 

3. Repeat 2 above with external controls set to maintain 

low fire.

4. If it is necessary to adjust either the high fire or low fire 

pressures proceed as follows after removing the plastic 

cover from the Modulating regulator.

Note: Minimum fire setting must be adjusted first 

after which the high fire setting can be set. Any 

adjustment of the minimum fire setting alters the 

maximum setting.

 

Minimum Setting

Disconnect electrical connection of modulating regulator 

and turn burners back on and wait until the burner pres-

sure has stabilized. Turn 9mm adjustment nut for low fire 

pressure clockwise to increase and counter-clockwise to 

decrease until the required pressure is obtained. Recon-

nect modulating regulator and check high fire pressure, 

readjust if necessary.

Maximum Setting

Disconnect electrical connection of modulating regulator 

and turn burners back on and wait until the burner pres-

sure has stabilized. Push shaft gently downwards to the 

maximum adjustment screw and hold there. Turn 7mm 

adjustment nut for high fire pressure, clockwise to 

increase and counter-clockwise to decrease, until the 

required pressure is obtained. Release shaft. Repeat both 

settings if necessary and then replace cover cap.

5. Turn off the main burner, disconnect the pressure 

gauge and replace the sealing screw. Turn on the main 

burner and test for gas soundness around pressure test 

joint using a leak detection fluid. Replace access panel.

2.6.6.2. Modulating Interface Board

 

Fig 8 Modulating Interface Board

The MIB interfaces between a 0-10VDC control signal 

and the modulating regulator. The following are applicable 

to this application.

1. The setting of the slide switches 1 & 2 should both be 

to OFF.

 

2. Potentiometer P1 (Default setting 100%)

The control current of the V7335A is controlled by P1, 

varying between 50% and 100% of the input signal.

E.g.

-When P1 is set at 100% (fully clockwise) maximum 

power (165mA @ 22VDC) is provided to the modulation 

coil with a 10VDC input control signal.

-When P1 is set at 50% (fully anticlockwise) maximum 

power (165mA @ 22VDC) is provided to the modulation 

coil with a 5VDC input control signal.

3. Potentiometer P2

Controls the minimum drop-out voltage between 0% and 

40% E.g.

- When P2 is set at 0% the drop-out voltage with an input 

control signal of 0-10V-DC is 0.3V-DC.

- When P2 is set at 40% the drop-out voltage with an input 

control signal of 0-10V-DC is 4.0V-DC.

4. Potentiometer P3 (Default setting 100%)

Controls the maximum hold-in voltage. Its proportional 

value is added to the P2 setting E.g.

- When P2 is set at 0% and P3 is set at 5%, the hold-in 

voltage of the burner relay is adjustable between 5% and 

100% of the input control signal. If the input control signal 

is set at 0-10V-DC the hold-in voltage of the relay is 

0.5V-DC.

- When P2 is set at 40% and P3 is set at 5%, the hold-in 

voltage of the burner relay is adjustable between 45% and 

100% of the input control signal. If the input control signal 

is set at 0-10V-DC the hold-in voltage of the relay is 

4.5V-DC.

The following table shows the relationship between P2 

and P3 settings.

2.6.6.2. Flame Current

1. To measure the flame current connect a multimeter 

capable of measuring micro amps as shown in the follow-

ing diagram. 

2. Minimum current reading is 0.5mA and normal value 

should be 1.5mA or higher.

Fig 8 Flame Current Measurement

 

2.6.6.3. Air Heater Controls

1. Close the gas service tap and ensure that the gas valve 

is heard to close within 1 second and that the lockout light 

is illuminated. Note that the heater may attempt five re-ig-

nitions before going to lockout. Open the gas service tap 

and reset the unit from lockout.

2. Check that the room thermostat and all automatic 

controls are operating satisfactorily.

2.6.7. Fan/Limit Thermostat

Thermostat settings:-

 

Fan Off 

Fan On  

Limit

NVx 10-140   86°F/30

o

C 122°F/50

o

C 212°F/100°C

 

Note: NVx 10 to NVx 75 units have one fan/limit  

thermostat whereas NVx 90 to NVx 140 units 

have two. The second thermostat is at the oppo-

site end of the heater to the burner/controls end. 

The fan circuits are wired in parallel (either 

thermostat will turn on the fan) and the limit 

thermostats are wired in series (either thermostat 

will shut down the burner)

2.6.8. Handing over the Air Heater

Hand these instructions to the user or purchaser for reten-

tion and instruct in the efficient and safe operation of the 

air heater and associated controls. Adjust the automatic 

controls to those values required by the User.

Finally, advise the user or purchaser that, for continued 

efficient and safe operation of the air heater, it is important 

that servicing is carried out annually.

In the event that the premises are not yet occupied turn 

off the gas and electricity supplies and leave instructional 

literature adjacent to gas meter.

Summary of Contents for NVx Series

Page 1: ...nstallation and Servicing Instructions Brahma Control MKIII LIB GM44 GB IE H E AT I N G V E NT I L AT I O N A I R C O N D IT I O N I N G WARNING THIS APPLIANCE MUST BE EARTHED IMPORTANT Reset from Loc...

Page 2: ...g company 4 The heater has been used in accordance with the manufactures instructions 5 The correct specification fuel has been used 6 No unauthorised repairs of modifications have been made 7 Powrmat...

Page 3: ...contact our Technical Support Team by calling 01460 53535 Users Installation and Servicing Instructions CONTENTS Title Section Contents Page User Instructions 4 Pre Installation 1 1 Introduction 5 1 2...

Page 4: ...controls e g Time clock room thermostat etc call for heat The internal exhaust fan will run and when sufficient combustion airflow is proved by the air pressure switch the ignition spark will be gener...

Page 5: ...or industrial premises All variants with the exception of NVx EA units are for internal use only NVx heaters feature a closed combustion circuit and have an internal exhaust fan mounted downstream of...

Page 6: ...from drop rods via purpose designed M10 suspension fixing points on the heater ii attached to our optional wall support brackets or iii positioned on a level non combus tible base In all cases it is i...

Page 7: ...ocal gas undertaking The inlet gas pressure under running conditions must not be less than 17 5mb 1 2 4 2 Meters An existing meter should be checked preferably by the gas undertaking to ensure that th...

Page 8: ...Installation 1 3 In the space Low Level Grille Free Area Low Level Grille Free Area High Level Grille Free Area Low Level Grille Free Area Low Level Grille Free Area High Level Grille Free Area High L...

Page 9: ...be provided If the air heater s is installed in a plant room the return air intake s and the warm air outlet s from the heater s must be fully ducted into and out of the plant room to avoid interferen...

Page 10: ...Page 10 NVX Range Users Instructions Service Instructions Issue 5 5 August 2015 1 3 Size Data NVx F Axial Fan Crossflow Units...

Page 11: ...00 700 760 100 233 5 492 142 317 450 232 5 925 206 114 297 1000 700 760 100 233 5 492 142 317 450 232 5 905 206 114 297 1000 700 912 100 233 5 644 142 317 450 232 5 925 206 114 374 1325 700 760 130 23...

Page 12: ...0 540 80 248 308 120 304 260 176 925 216 114 194 1000 700 760 100 233 5 492 142 283 260 197 925 206 114 297 1000 700 760 100 233 5 492 142 283 260 197 905 206 114 297 1000 700 912 100 233 5 644 142 28...

Page 13: ...4 1000 700 760 100 233 5 492 142 317 450 232 5 1430 206 114 297 1000 700 760 100 233 5 492 142 317 450 232 5 1430 206 114 297 1000 700 912 100 233 5 644 142 317 450 232 5 1430 206 114 374 1325 700 760...

Page 14: ...0 700 760 100 233 5 492 142 317 450 232 5 835 206 114 297 1000 700 760 100 233 5 492 142 317 450 232 5 835 206 114 297 1000 700 912 100 233 5 644 142 317 450 232 5 835 206 114 374 1325 700 760 130 235...

Page 15: ...al Fan Bi Directional Units Model A B C D E F G H J K L M N P mm mm mm mm mm mm mm mm mm mm mm mm mm mm 2325 700 700 130 235 5 356 220 347 850 278 1120 246 88 260 2325 700 831 130 235 5 487 220 347 85...

Page 16: ...e heater Top of heater Rear of heater Dependant on flue system used For Multi air heater Installations the following minimum distances between units must be observed Between units side to side Between...

Page 17: ...umstances must these points be used as the final means of suspension 2 1 2 Suspending the heater Threaded drop rods must have lock nuts fitted that are tightened down onto the 10mm fixings in the heat...

Page 18: ...n sealant around the face of the flange of the combustion air socket on the same side as the socket Passing the socket through the panel from the inside position the flange up against the panel Secure...

Page 19: ...centric adaptor to the terminal section and then extend down to the heater using straight lengths Fit adjustable lengths as the final connection pieces to facilitate flue disconnection for servicing E...

Page 20: ...ustable length Single to twin adaptor Flue socket Combustion air duct Maximum 6m Minimum 980mm Combustion air socket Note A terminal guard may be required Type C12 installation Type C32 installation P...

Page 21: ...ly sized See the wiring diagram accompanying these instructions Models supplied with a centrifugal fan silencer duct section require wiring to be completed between the heater and fan Refer to supplied...

Page 22: ...ss before leaving the factory After establishing the main burners test round the gas inlet connection using a leak detection fluid 1 Switch on the electrical supply at the isolator 2 If the limit indi...

Page 23: ...nal CO2 values are given for guid ance in the Table at the bottom of the previous page 5 Turn off the main burner and disconnect the pressure gauge and replace the sealing screw Turn on the main burne...

Page 24: ...as meter dial pointer ensuring that no other appliances supplied through the meter are in operation 3 Repeat 2 above with external controls set to maintain low fire 4 If it is necessary to adjust eith...

Page 25: ...ignal of 0 10V DC is 0 3V DC When P2 is set at 40 the drop out voltage with an input control signal of 0 10V DC is 4 0V DC 4 Potentiometer P3 Default setting 100 Controls the maximum hold in voltage I...

Page 26: ...Controls 1 Close the gas service tap and ensure that the gas valve is heard to close within 1 second and that the lockout light is illuminated Note that the heater may attempt five re ig nitions befo...

Page 27: ...2 7 4 Heat Exchanger Whilst the main burner assembly is removed from the unit check that the primary sections that the burners fire into are clean 2 7 5 Main Fan Assembly 2 7 5 1 NVx F CCF Models 1 In...

Page 28: ...at settings Fan Off Fan On Limit NVx 10 140 86 F 30o C 122 F 50o C 212 F 100 C 1 Squeeze the casing sides inward and pull casing forward 2 Remove the electrical connections from the thermostat 3 Remov...

Page 29: ...e 2 Electrical Loading 1ph NVx90 NVx120 5 00 2 30 7 80 3 80 NVx140 7 80 3 80 F Models CCF Models MODEL PLATE AMPS A START AMPS A RUN AMPS A FUSE RATING A NVx10 2 NVx15 0 18 0 34 0 16 910 2 8 4 2 2 10...

Page 30: ...00 183 F CCF HIGH FIRE LOW FIRE AIR VOLUME MAXIMUM DUCT RESISTANCE FAN MOTOR WEIGHT NVx60 65 60 60 0 32 80 27 88 1 5608 N A 0 680 135 5 250 1 40 213 NVx75 NVx90 NVx120 81 30 75 0 95 3 90 0 130 1 120 0...

Page 31: ...8 59 2 8 4 50 NVx90S 10 2 83 950 8 0 10 35 2 8 6 06 NVx90 6 3 5 1500 9 4 10 07 3 5 6 19 NVx120 8 3 5 1500 9 1 13 77 4 1 9 30 NVx140 10 3 5 1500 8 4 15 74 4 0 10 46 Minimum Inlet Pressure 37mbar Inlet...

Page 32: ...t reset when cold check for for 230V between terminals 9 11 on the limit interface board Check connections faulty limit stat Gas Electrical supplies present Unit at Lockout Lockout lamp on low level c...

Page 33: ...more ignition attempts then lock out Exhaust fan continues to run APS has lost C to N O continuity slightly reduce APS set point Check for 230V between terminals 13 N of the terminal strip Absent Rep...

Page 34: ...120 140 141378715 Ignition Electrode 10 75 142423002 Ignition Electrode 90S 90 140 142423004 Rectification Electrode All 142423003 Burner 10 75 142400240 Burner 90S 90 140 142400241 Fan Limit Thermost...

Page 35: ...04 Z 15 35 40 140232005 Z 15 50 90 140232006 Z 15 60 75 120 140 140232007 Z 15 90S 140232011 Main air fan Axial NVx V 10 15 140232002 Z 15 20 140232010 Z 15 30 40 140232009 Z 50 90 140232018 60 75 120...

Page 36: ...press However as part of our policy of continued product improvement we reserve the right to alter specification without prior notice Page 36 NVX Range Users Instructions Service Instructions Issue 5...

Reviews: