PowerWalker VFI 3/3 Series

VFI 20000TP~40000TP 3/3 BX

380/400/415V  50/60Hz

(3-phase input/output)

User Guide

Summary of Contents for VFI 20000TP 3/3 BX

Page 1: ...PowerWalker VFI 3 3 Series VFI 20000TP 40000TP 3 3 BX 380 400 415V 50 60Hz 3 phase input output User Guide...

Page 2: ......

Page 3: ...of the publisher and may not be reproduced even extracts unless permission granted Every care has been taken to ensure the accuracy of the information contained in this manual but no liability can be...

Page 4: ...uisher should be used properly Using liquid fire extinguisher may result in electric shock hazard 8 Storey bearing capacity of machine and batteries should be taken into consideration prior to install...

Page 5: ...ll cause damages to both human skins and eyes Should electrolytes come into any contact with human body unintentionally rinse with clean water and seek medical advice 7 Do not cause battery positive a...

Page 6: ...g inspection 2 2 Outside view drawing 2 3 Panel instructions Chapter 4 Operation 3 1 Single machine installation 3 2Parallel machine installation 3 3 Procedures of connecting battery box to UPS 4 1 Si...

Page 7: ...financing transportation government manufacturing and energy sectors PowerWalker VFI 3 3 Series products are also capable of ECO mode Under ECO mode UPS is powered by AC supply while in case of abnorm...

Page 8: ...re up to the following safety standards The Series products are up to the following level of EMC requirement Remark Proper attention should be given to all warning symbols on the equipment and no tear...

Page 9: ...Unbalanced load capacity 100 Battery voltage and charging voltage WARNING This is a product for commercial and industrial application in the second environment installation restricitions or additional...

Page 10: ...suggested that prior to start up of UPS environmental temperature should be brought back to 0 or above for 2 hours Altitude below 1000m Storage temperature 25 55 MODEL NO Machine size mm L W H N W kg...

Page 11: ...the following figure for the dismantling of machine cabi net 1 Unpack and there should be 2 1 Unpacking inspection 2 Check whether UPS is damaged during the process of transportation or not Should an...

Page 12: ...TERYTEMP PROBE Fan Front view Rear view SERVICE RS232 RS485 EPO AS400 Exterior figure of VFI 20000TP 3 3 BX UPS 2 2 Exterior figure LCD panel Button LED indicator light intelligent slot Extended slot...

Page 13: ...0TP 3 3 BX UPS CHGR FAN Maintenance switch Main Main Optional kit Front view without front panel EXT BATTERYTEMP PROBE FAN SERVICE RS232 RS485 EPO AS400 Front view Rear view LCD panel Button LED indic...

Page 14: ...en UPS is powered directly by AC Inverter this light will turn green when UPS is loaded through the inverter Battery this light will turn yellow when UPS is powered by batteries Bypass this light will...

Page 15: ...Confirm Enter press this button to select a menu or confirm an operation PageDown press this button to switch to next screen display under the same menu PageUp press this button to return to next scre...

Page 16: ...ture for normal UPS performance should not exceed 50 4 It is suggested that battery pack should work within a temperature range from15 to 25 5 Altitude for normal UPS function should not exceed 1000m...

Page 17: ...down to the ground keeping the machine from moving Optional kit Machine Model Rated power input live wire Diameter Input switch Output live wire Diameter Battery positive and negative wire Diameter b...

Page 18: ...er supervising software on PC 1 Follow installation instructions for general installation requirements 2 Ventilation spacing between machine flanks should be a minimum of 10cm and a mini mum of 50cm c...

Page 19: ...Use multimeter DC Voltage to measure the voltage of positive and negative batteries as well as positive and negative polarity 3 3 Procedures of connecting battery box to UPS Remark remove the panel on...

Page 20: ...input breaker Main bypass input breaker Main if assembled on UPS and fans start to rotate for UPS self inspection Main menu can be accessed within about 4sec and then operations should be carried Rema...

Page 21: ...EN 5 Press again to obtain the below 6 Press again to obtain the below information information 7 Press again to obtain the below 8 Press again to obtain the below information information VFI 20000TP 3...

Page 22: ...the machine Remark when malfunction occurs x will appear at the lower right corner of the pic ture while when warning occurs will appear at the same position as illustrated in the below picture with...

Page 23: ...C to exit above picture 1 Switch off picture 2 If it is in single machine mode the following will appear 3 If it is in parallel machine mode the 4 Press ENTER following will appear 5 Battery power sup...

Page 24: ...witch off only one set of UPS among the parallel machine sys tem select single machine switch off if switch off is intended for the entire parallel machine system select parallel machine switch off 5...

Page 25: ...pass power supply 2 Press 7 Setting action press ESC to exit the above picture You are able to access Setting picture by using user combination default 1234 subject to personal modification so as to s...

Page 26: ...structions appearing in the pictures 9 Procedures of DC switch on Activate DC switch on function set under UPS bypass mode Make sure that and N wires of batteries are properly connected to UPS Switch...

Page 27: ...unit when one set of UPS breaks down with malfunction the remaining four sets will provide power with al most 14kVA equalized current if two sets of UPS fail the remaining three sets of UPS are suppos...

Page 28: ...al operation 2 After switch to Line mode all machines will jump to conversion mode switch off when switch off is conducted under conversion mode all machines will simultaneously switch off inverter an...

Page 29: ...et capable of battery temperature supervision so as to realize battery intelligent management 5 Standard AS400 interface provides AS400 and users can directly use UPS supervising function offered by A...

Page 30: ...24 RS485 port RS232 port...

Page 31: ...25 EN AS400 port...

Page 32: ...ies should be found in poor performance replace ment should be done as soon as possible only by qualified personal with proper training Users are not allowed to replace without authorization Remark A...

Page 33: ...odel serial number as well as pur chase date symptom on fault light condition LCD malfunction or warning information Troubleshooting Should maintenance prove necessary the following steps should be fo...

Page 34: ...28 Appendix 1 Light Reference Table Should any display or warning message excluded in the above table be found please con tact distributor Indicator light is on Indicator light flashes...

Page 35: ......

Page 36: ...614 01720 00...