background image

21 

 

3-4. Single UPS Operation 

1. Turn on the UPS with utility power (in AC mode)   

1)    After power supply is connected correctly, set the breaker of the battery pack at “ON” position (this step 

only necessary for long-run model). Then set the line input breaker at “ON” position. At this time the fan 

is running and the UPS enter to power on mode for initialization, several seconds later, UPS operates in 
Bypass mode and supplies power to the load via the bypass. 

 

NOTE: 

When UPS is in Bypass mode, the output voltage will directly power from utility after you switch 

on the input breaker. In Bypass mode, the load is not protected by the UPS. To protect your precious 

devices, you should turn on the UPS. Refer to next step.   

2)    Refer to 

Screens 1.1-1.

 

3)  A few seconds later, the UPS will enter into AC mode. If the utility is abnormal, the UPS will operate in 

Battery mode without interruption. 

NOTE: 

When the UPS running out battery, it will shut down automatically at Battery mode. When the utility 

is restored, the UPS will auto restart in AC mode.   

2. Turn on the UPS without utility power supply (in Battery mode) 

1)    Make sure that the two strings of batteries are connected correctly at UPS’s ”+,GND,-” terminals and the 

breaker of the battery pack is at “ON” position (only for long-run model).   

2)    Press the “Power-On” button to set up the power supply for the UPS. UPS will enter to power on mode. 

After initialization, UPS will enter to No Output mode, then refer to 

Screens 1.1-1.

 

3)    A few seconds later, the UPS will be turned on and enter to Battery mode. 

3. Connect devices to UPS 

After the UPS is turned on, you can connect devices to the UPS. 
1)    Turn on the UPS first and then switch on the devices one by one. The LCD panel will display total load 

level.   

2)    If it is necessary to connect the inductive loads such as a printer, the in-rush current should be calculated 

carefully to see if it meets the capacity of the UPS, because the power consumption of this kind of loads 

is too big.

 

3)    If the UPS is overload, the buzzer will beep twice every second. 
4)    When the UPS is overload, please remove some loads immediately. It is recommended to have the total 

loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system 

safety.   

5)    If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically transfer 

to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is over 

acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if bypass is 

enabled, the UPS will power to the load via bypass. If bypass function is disabled or the input power is 
not within bypass acceptable range, it will cut off output directly. 

4. Charge the batteries 

1)    After the UPS is connected to the utility power, the charger will charge the batteries automatically except 

in battery mode or during battery self-test or overload or battery high voltage.   

2)    Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter 

than expected. 

5. Battery mode operation 

1)    When the UPS is in Battery mode, the buzzer will sound according to different battery capacity. If the 

battery capacity is more than 25%, the buzzer will beep once every 4 seconds. If the battery voltage 

drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the battery is 

at low level and the UPS will shut down

 

automatically soon. Users could switch off some non-critical 

loads  to  disable  the  shutdown  alarm  and  prolong  the  backup  time.  If  there  is  no  more  load  to  be 

switched off at that time, you have to shut down all loads as soon as possible to protect the devices or 

save data. Otherwise, there is a risk of data loss or load failure.   

2)    In Battery mode, if buzzer sound annoy, users can press the Mute button to disable the buzzer. 
3)    The backup time of the long-run model depends on the external battery capacity. 
4)    The backup time may vary from different environment temperature and load type. 
5)    When setting backup time for 16.5 hours (default value from LCD menu), after discharging 16.5 hours, 

Summary of Contents for VFI 10KL CPG PF1 3/3

Page 1: ...PowerWalker VFI 10K 80K CPG PF1 3 3 Uninterruptible Power Supply System Version 1 0 1...

Page 2: ...E 26 5 2 MAINTENANCE 26 6 SPECIFICATIONS 27 Please comply with all warnings and operating instructions in this manual This equipment should only be installed serviced and maintained by qualified perso...

Page 3: ...n the final installation phase connect grounding wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An approp...

Page 4: ...g conductor cable on the UPS or the building wiring terminals under any circumstance The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks...

Page 5: ...lowing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package should contain One UPS One user manual One monitoring software CD option please check...

Page 6: ...4 2 2 Wiring Terminal View Diagram 1 10K 15K 20K L Diagram 2 10K 15K 20K L Rear Panel DUAL Rear Panel Diagram 3 10K 15K 20K L Diagram 4 10K 15K 20K L Input Output Terminal DUAL Input Output Terminal...

Page 7: ...5 Diagram 5 30K L Rear Panel Diagram 6 40K L Rear Panel Diagram 7 30K L 40K L Dual Input Input Output Terminal...

Page 8: ...6 Diagram 8 60KL front view Diagram 9 80KL front view with door open with door open Diagram 10 60KL 80KL Input Output Terminal...

Page 9: ...e as the input power source for the UPS as its rated current is less than the UPS s maximum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building befo...

Page 10: ...15K L 20K L Terminal block wiring diagram for 10K L 15K L 20K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram HV 60KL 80KL T...

Page 11: ...ion to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The Connection with wrong battery...

Page 12: ...gram of parallel system for 10K L 15K L 20K L a Wiring diagram of parallel system for 10K L 15K L 20K L Wiring diagram of parallel system for 30K L 40K L Wiring diagram of parallel system for 30K L DU...

Page 13: ...iring diagram of parallel system for 60KL 80KL 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation Please download the...

Page 14: ...er into the sub screen MAIN Initializing INFORMATION CONTROL SETTING DATA LOG MEASURE ON OFF UPS BATTERY TEST MUTE ALL MEASURE1 MEASURE2 MEASURE3 BASIC ADVANCE BASIC1 BASIC2 ELECTRICAL BATTERY MISCELL...

Page 15: ...n 0 0 Screen 1 0 Control screen with common control operation Screens 1 1 1 to start and stop the unit through the control panel Enter YES to turn on or turn off UPS And screen will jump to main scree...

Page 16: ...attery test are Battery testing The battery test is running Battery Test failed The battery test has been failed Screen 1 1 3 to order cancel mute of UPS Enter YES to make UPS mute Press BACK or No ic...

Page 17: ...hases to neutral for three phase or single phase units 0 1V Bypass voltages phase to phase units 0 1V Bypass voltages phases to neutral for three phase or single phase units 0 1V Output voltages phase...

Page 18: ...can program the time hh mm ss hours minutes seconds and the date dd mm yy day month year You can select the display language between the available options it may vary You can select input source Line...

Page 19: ...level an authorized password will be required to modify some advanced parameters Screens 3 1 2 Advance settings Screens 3 1 2 1 You can select the output voltage between the following options 208V 220...

Page 20: ...an select the ECO frequency range The range of frequency goes from 46Hz to 54Hz when UPS is 50Hz system and goes from 56 Hz to 64 Hz when UPS is 60Hz system You can select Whether UPS is enable or dis...

Page 21: ...rmation To modify the rated values on the screens it is necessary to introduce the Password on the previous screen 3 0 otherwise they only will be able to be visualized The basic information shows UPS...

Page 22: ...ere are all the possible alarms displayed in the display LCD 3 3 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4...

Page 23: ...f the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 8...

Page 24: ...ns that there are problems for UPS operation Users can get the warning indicator from LCD panel Please check the trouble shooting table in Chapter 4 for details 2 Some warning alarms can t be muted un...

Page 25: ...er the UPSs enter to Battery mode and add to the parallel system d If you have the third UPS follow the same procedure of c Then the parallel system is complete If more detail information is needed pl...

Page 26: ...e short circuited None 64 Voltage waveform abnormal in B phase None 18 Inverter B C output line to line short circuited None 65 Voltage waveform abnormal in C phase None 19 Inverter C A output line to...

Page 27: ...ed position to disable the EPO function The warning code 01 The external or internal battery is incorrectly connected Check if all batteries are connected well The warning code 09 UPS is overload Remo...

Page 28: ...acks which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the te...

Page 29: ...7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah N A Numbers 10 10 pcs 16 16 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 2 0 A 10 Recommended 1 0 12 0A Adjustable Charging Vol...

Reviews: