USER MANUAL 

 

 

On-Line UPS 

 
 

1000VA/1500VA/2000VA/3000VA 

 
 
 
 
 
 
 

 
 

 

 

 
 
 

 

         

 

 
 
 
 

 

Uninterruptible Power Supply System 

 
 

Summary of Contents for VFI 1000RT

Page 1: ...USER MANUAL On Line UPS 1000VA 1500VA 2000VA 3000VA Uninterruptible Power Supply System...

Page 2: ...19 5 2 Connection 19 5 3 Battery charge 21 5 4 Turn on the UPS 21 5 5 Test function 21 5 6 Turn off the UPS 22 5 7 Audible alarm mute function 22 5 8 Operation procedure of external battery for long...

Page 3: ...33 10 3 Typical backup time Typical values at 25 C in minutes 33 10 4 Dimensions and weights 34 11 Communication Port 35 11 1 RS 232 and USB communication ports 35 11 2 RS 232 port 35 11 3 USB port 3...

Page 4: ......

Page 5: ...er serviceable parts inside Refer servicing to qualified service personnel The utility power outlet shall be near the equipment and easily accessible To isolate UPS from AC input remove the plug from...

Page 6: ...Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be theref...

Page 7: ...e Cabinet To unpack the system 1 Open the outer carton and remove the accessories packaged with the cabinet 2 Carefully lift the cabinet out of the outer carton and set it on a flat stable surface 3 D...

Page 8: ...4 EN 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel...

Page 9: ...UPS into the rack rail and lock it in the Rack mounting 4 Tighten the screw and then the load can be connected 1 1 4 EBM Installation Optional Connecting the EBM in Tower form 1 Slide down the UPS and...

Page 10: ...6 EN on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel B A C B A...

Page 11: ...to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel 5 After installing the UPS into rack the load can th...

Page 12: ...el to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel Connecting the Multiple EBMs in rack form 1 Connect Earth line between UPS and the first EBM and then co...

Page 13: ...ration as this would remove the ground to the UPS and of all connected loads The UPS features its own internal current source batteries You may be electric shock when you touch the UPS output sockets...

Page 14: ...st be replaced only by qualified personnel Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 15: ...ff the UPS and disconnect the utility power cord from the wall outlet Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized...

Page 16: ...e from the UPS and battery pack 4 Remove the right inner battery bracket 5 Pull the battery pack out onto flat area 6 Install new battery pack into UPS 7 Screw up the battery bracket and reconnect the...

Page 17: ...iscard the UPS battery pack and batteries into the trash bin Please follow your local laws and regulations you may contact your local recycling waste management center for further information to dispo...

Page 18: ...y C1 Harmonic Current IEC EN 61000 3 2 Voltage Fluctuation and Flicker IEC EN 61000 3 3 EMS ESD IEC EN 61000 4 2 Level 3 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5...

Page 19: ...15 EN 2 Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Page 20: ...s and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the m...

Page 21: ...ches to No output or Bypass mode by pressing OFF Button and the inverter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power...

Page 22: ...g It indicates the Number of the input supplied from the mains It indicates the Number of the output connected with load Battery Information Load Information It indicates the battery capacity Every gr...

Page 23: ...ecommended to select the 2 5mm 2 wire and the GND terminal should be grounded first The UPS System has no input breaker on the standard cabinet When installing the UPS the user needs to connect the ex...

Page 24: ...2 wires for wiring configuration c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the rear panel 3 EPO Connection User ca...

Page 25: ...ate the state of the UPS 2 Without utility power connecting If UPS is cold start without utility power connecting user need to push I button twice first pushing I button is for UPS to get power LCD sc...

Page 26: ...rned off completely 5 7 Audible alarm mute function If the alarm is too annoying in battery mode you may press I button continuously for more than 1 second to clear it Moreover the alarm will be enabl...

Page 27: ...s following GND Red wire Green Yellow wire Black wire 6 The red wire is connected to the terminal of the battery The black wire is connected to the terminal of the battery Note the green yellow wire i...

Page 28: ...ous warnings would not be shown again but only the fault string is presented Normal operating mode Code No output mode STbY Bypass mode bYPA Line mode LINE Battery mode bATT Battery test mode TEST ECO...

Page 29: ...er the battery level the UPS output and the load level could be displayed The bATT string indicates the UPS is working in the battery mode When the UPS is running in battery mode the buzzer beeps once...

Page 30: ...d alarm The UPS could not be turned off by pressing OFF button on the panel only after releasing EPO status by turning off the EPO switch 6 6 ECO mode Economy mode It is also called high efficiency mo...

Page 31: ...continuously by the battery 1 It could be enabled through the LCD setting or the software Winpower etc 2 The load should be derating to 70 in converter mode 6 8 Abnormal mode In abnormal mode such as...

Page 32: ...tage press the Enter button for more than one second a flickering string 208 would be shown if the Enter button is pressed again the string 208 turn to flickerless the output volt is changed to 208V i...

Page 33: ...ere 000 means load segment 1 off 001 means load segment 1 on Load segment 2 is the same as Load segment 1 Here is a example for changing the Operating mode from normal mode to converter mode through t...

Page 34: ...ndication no warning tone even though system is connected to mains power supply No input voltage Check building wiring socket outlet and input cable Display Mode string STbY in LCD even though the pow...

Page 35: ...rn off the EPO switch Bus fault Low high Unbalance soft start UPS internal fault Notify dealer Inverter fault Low high soft start UPS internal fault Notify dealer Over temperature fault Over temperatu...

Page 36: ...ified personnel It recommends to shut off the UPS completely before the replacement If there is a battery breaker then turn it off first Disconnect the battery cable carefully and make sure no any exp...

Page 37: ...mperature 0 C to 40 C Operating humidity 95 Altitude 1000m Storage temperature 0 C to 45 C Specyfikacja elektryczna Phase 1 Cz stotliwo 45 55 54 66 Hz Max Current A 7 5 10 5 13 5 20 WYJ CIE WEJ CIE Mo...

Page 38: ...00S 2000 2000S 3000 3000S UPS Case Net weight kg 16 2 8 4 19 7 9 3 19 7 9 3 28 6 13 2 Dimension mm W x H x D 438X86 5x436 438X86 5x608 EBM Case Dimension mm W x H x D Net weight kg 22 2 27 5 40 5 Type...

Page 39: ...ified in the following illustration RS 232 communication port pin assignments Pin Signal name Function Direction from the UPS 1 Unused Not applicable 2 Tx Transmit to external device Out 3 Rx Receive...

Page 40: ...bay cover to the UPS and save the screws 3 Insert the Serial Network Management Card into the slot on the UPS 4 Secure the Serial Network Management Card to the UPS with both screws For more informat...

Page 41: ...y warning happens On Battery Activated when the UPS operates on battery Battery Low Activated with the bLOW alarm UPS ok Activated when the UPS has no alarms and no fault On Bypass Activated when the...

Page 42: ...can remotely observe the UPS via the Network enabling users to manage their system more effectively Upon AC failure or UPS battery low UPS takes all necessary actions without intervention from the sy...

Page 43: ...00VA 1500VA 2000VA Standard 1000VA 1500VA Super charger model rear panel 2000VA Super charger model rear panel No Function 1000VA 1500VA 2000VA 3000VA 1 AC Output 2 EPO Dry in Communication Port 3 USB...

Page 44: ...ion 36V 48V 72V EBM 1 Earth Line Port 250V 10A 250V 10A INTELLIGENT SLOT RS232 LS2 AC OUTPUT LS1 AC OUTPUT 250V 16A USB AC INPUT DRY IN EPO DRY OUT EPO DRY IN DRY OUT USB RS232 INTELLIGENT SLOT USECO...