01: Output voltage   

Interface Setting 

 

Parameter 3: Output voltage 

You may choose the following output voltage in parameter 3: 

208: 

Presents output voltage is 208Vac 

220:

 Presents output voltage is 220Vac 

230:

 Presents output voltage is 230Vac 

240: 

Presents output voltage is 240Vac 

z

 

02: Output frequency   

Interface Setting 

60 Hz, CVCF mode 

 

50 Hz, Normal mode 

 

ATO 

 

Parameter 2: Output Frequency 

Setting the output frequency. You may choose following three 

options in parameter 2: 

50.0Hz: 

The output frequency is setting for 50.0Hz.   

60.0Hz:

 The output frequency is setting for 60.0Hz. 

ATO:

 If selected, output frequency will be decided according to 

the latest normal utility frequency. If it is from 46Hz to 54Hz, the 

output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the 
output frequency will be 60.0Hz. ATO is default setting. 

 

Parameter 3: Frequency mode 

Setting output frequency at CVCF mode or not CVCF mode. You 

may choose following two options in parameter 3: 

CF:

 Setting UPS to CVCF mode. If selected, the output frequency 

will be fixed at 50Hz or 60Hz according to setting in parameter 2. 

The input frequency could be from 46Hz to 64Hz. 

NCF:

 Setting UPS to normal mode (not CVCF mode). If selected, 

the output frequency will synchronize with the input frequency 

within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to 

setting in parameter 2. If 50 Hz selected in parameter 2, UPS will 

transfer to battery mode when input frequency is not within 
46~54 Hz. If 60Hz selected in parameter 2, UPS will transfer to 

battery mode when input frequency is not within 56~64 Hz.   

*If Parameter 2 is ATO, the Parameter 3 will show the current 

frequency. 

z

 

03: Voltage range for bypass   

Interface Setting 

 

Parameter 2: 

Set the acceptable low voltage for bypass. Setting 

range is from 110V to 209V and the default value is 110V. 

Parameter 3: 

Set the acceptable high voltage for bypass. Setting 

range is from 231V to 276V and the default value is 264V. 

z

 

04: Frequency range for bypass 

Interface Setting 

 

Parameter 2:

 Set the acceptable low frequency for bypass.   

50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 

60 Hz system: Setting range is from 56.0Hz to 59.0Hz. 
The default value is 46.0Hz/56.0Hz. 

Parameter 3: 

Set the acceptable high frequency for bypass.   

50 Hz: Setting range is from 51.0Hz to 54.0 Hz.   

60 Hz: Setting range is from 61.0Hz to 64.0Hz. 
The default value is 54.0Hz/64.0Hz. 

Summary of Contents for Centurion PSCER10000

Page 1: ...Centurion 6000 10000 VA Rack Online UPS Users Manual www powershield com au...

Page 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Page 3: ...ngs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading throug...

Page 4: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 UPS OPERATION 12 3 5 ABB...

Page 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Page 6: ...onnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Page 7: ...One PowerShield NetGuard UPS monitoring software CD One RS 232 cable One USB cable One EPO plug Fitted on the rear panel NOTE Before installation please inspect the unit Be sure that nothing inside t...

Page 8: ...nput power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building befor...

Page 9: ...re installation NOTE Set the battery pack breaker in OFF position and then install the battery pack Pay attention to the rated battery voltage marked on the rear panel If you want to change the number...

Page 10: ...CVCF mode UP key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9...

Page 11: ...cates that the UPS alarm is disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information I...

Page 12: ...ce every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Yes Warning Overload Beeping twice every second Low battery Battery unconnected Over charge EPO enable Fan...

Page 13: ...e UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the...

Page 14: ...when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test auto...

Page 15: ...battery and output immediately to avoid more risk or danger 12 Operation of changing battery numbers 1 This operation is only available for professional or qualified technicians 2 Turn off the UPS If...

Page 16: ...t 01 Output voltage Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 ECO mode enable disable Y 06 Voltage range for ECO mode Y 07 ECO mode frequency range setti...

Page 17: ...ting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output frequency will synchronize with the input frequency within 46 54...

Page 18: ...Parameter 3 Set high voltage point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz z 08 Bypass mode setting...

Page 19: ...programmable output Interface Setting These functions are not supported by the Rack model z 12 Reserved Interface Setting Reserve for future options z 13 Battery voltage adjustment Interface Setting...

Page 20: ...ttery specifications z 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6 4V the default valu...

Page 21: ...de LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD display Desc...

Page 22: ...start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 Inverter output short circuited 14 3 9 Warning I...

Page 23: ...is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights o...

Page 24: ...most common problem 3 If the problem still persists please call 1300 305 393 for technical support or fill in the form in PowerShield web page for on line technical support Following details are need...

Page 25: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Page 26: ...recover to 90 capacity Charging Current 2 0 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 2 0 A 10 max Long run Model Charging Voltage...

Page 27: ...37 100350 00G...

Reviews: