background image

The Series e700 HydroGuard T/P automatically mixes
hot and cold water to deliver blended water within a
specified range. Using an advanced thermal actuator,
the Series e700 quickly compensates for temperature
fluctuations induced by water temperature and pres-
sure changes. In the event of cold water failure, the
thermostatic motor virtually shuts off the flow of hot
water. HydroGuard T/P meets the most stringest per-
formance criteria for temperature and pressure
changes, defined by ASSE 1016 (Type T/P). 

Featuring heavy, cast-brass construction and an
adjustable brass to brass high limit temperature stop,
self-contained cartridge, corrosion resistant internal
component, integral checks, and back to back shal-
low wall installation capability. All parts of the e700
Series valve are accessible from the front of the valve.
All Series e700 valves open in the cold water position
to ensure maximum bather safety and comfort.

The accuracy, reliability and water economy of the
Series e700 HydroGuard T/P make it preferable for

TECHNICAL INSTRUCTIONS

DESCRIPTION

SPECIFICATIONS

Valve Construction:

Combination mixing valve, with heavy cast bronze body and brass stem. Concealed adjustable

high temperature limit stop. Available with ADA-compliant ABS or metal lever handle.

Connections 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/2” Sweat Inlet/Outlet

Capacity

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 gpm @ 45 psi 

Δ

P 50/50 mix

Maximum Hot Water Supply Temperature

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190

°

F(88

°

C)

Minimum Hot Water Supply Temperature (Approach Temperature) 

. . . . . . . . . . . 10°F (5.5°C) above set point

Maximum Operating Pressure

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 psig (862 kPa)

Temperature Ranges 

(for +/- 3°F performance). . . . . . . . . . . . . . . . . . . 

ASSE 1016 Type T/P

: 90 - 110°F (32 - 43°C)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

ASSE 1016 Type T

: 80 - 120°F (27 - 49°C)

High Temperature Limit Stop

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjustable (factory set at 110°F [43°C])

Maximum Static Pressure

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 psig (862kPa)

Minimum Flow

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 gpm (1.89 L/min)

Certified

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CSA B125

Listing

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1016

Shipping Weight

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 lbs. (1.6 kg)

All  HydroGuard T/P Series e700 combination mixing valves meet above performance specifications based on typical
operating conditions as stated in ASSE 1016 (45 psi pressure differential, hot water supply between 140°-180°F (60°-
82°C), cold water supply less than 70°F (21°C).

If your operating conditions vary from those stated in the standard, performance may vary as well. Consult your local
sales representative or a Powers factory engineer to discuss your specific application. All Powers thermostatic mixing
valves perform to the requirements of standards ASSE 1016 and CSA B125.

applications that require precise, consistent water 
control: showers, baths, hospital hydrotherapy and 
residential areas. All e700 valves meet the 

Americans

with Disabilities Act (ADA).

e710

e705

e707

Series e700

TI-e700