13.1 Installing new modules
Install new modules according to following steps:
1.Plug in module
2.Ignore the module alarm caused current sharing
3.Wait. After 1 minute the yellow LED will start blinking. Wait for max. 4 min
4.Verify that yellow LED stops blinking
5.The alarm should now disappear
6.Tighten front screw
13.2 Troubleshooting
This guide is a step-by-step recommendation of what to do if problems occur. If first step of
recommendation do not solve the problem continue to the next one. If the problem cannot be solved please
call your local Power - One office for assistance.
Note!
Before Commissioning and Maintenance are carried out a PC with PowCom installed must be
connected to the RS232 contact (Only applies when a controller without LCD display is in use).
Low system voltage:
z
Check the batteries with a voltmeter.
z
Check "low volt alarm" limit in controller / PowCom.
z
Check that the system is not in battery "test mode".
z
Check modules, mains and load situation compared to rectifier capacity.
High system voltage:
z
Check the batteries with a voltmeter.
z
Check "High volt alarm" limit in controller / PowCom.
z
Check that the system is not in "boost/Charge mode".
Load/battery disconnected:
z
Verify that input mains is present
z
Check system DC voltage with voltmeter
z
Compare system DC voltage with disconnected thresholds in controller / Powcom.
z
If breaker blows once more, there is either a too high load or short circuit at the system
Mains error:
z
Check mains breakers.
z
Check mains voltage.
Distribution breaker failure:
z
Localise the blown breaker.
Summary of Contents for PODS 16.48-16000 1940 HEX
Page 4: ...1 2 PODS 16 48 16000 1940 HEX Document number titlepage fm Revision B...
Page 10: ...2 6 PODS 16 48 16000 1940 HEX Document number 039158TOC fm Revision B...
Page 23: ...Safety 5 1 Document number 028580 fm Revision A Safety 5 Safety...
Page 40: ...6 14 PODS 16 48 16000 1940 HEX Document number 039160 fm Revision A Installation guide...
Page 41: ...Commissioning 7 1 Document number 036285 fm Revision A Commissioning 7 Commissioning...
Page 92: ...A 10 PODS 16 48 16000 1940 HEX Document number Appendix A fm Revision B Drawings...
Page 94: ...B 2 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...
Page 95: ...Configuration c 000313 B 3 Document number 039418 fm Revision B Configuration c 000313...
Page 96: ...B 4 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...