Installation guide
6-13
Document number: 039160.fm
Revision: A
Installation guide
6.2.9.1
Battery tube routing
The ventilation tube from the battery should be routed out of the cabinet through the cable entry casing as
shown in
. Pull the tube through the cable entry casing from the inside, and attach a tube
extension piece to avoid the tube sliding back inside the cabinet.
Note!
Nipples on cable entry casing not shown in
Figure 6-9 Battery tube routing
6.2.10 DC connection
This section details how to connect external load to the DC load breakers.
Check that all the MCB’s are in the OFF position.
1. Connect the negative (-) DC supply cable to the appropriate negative DC distribution MCB by
inserting the stripped cable in the opening on top of the MCB and tightening the screw.
2. Make sure the cable has the correct rating (i.e. thick enough) for the selected MCB.
3. Connect the positive (+) DC supply cable directly to the positive bus bar by inserting the stripped
cable to the hole on top of the screw connector so that the cable is behind the bus bar, and then
tightening the screw.
4. Start connecting the loads to the bus bar from the first connector on the left. Make sure the cable is
the correct rating (i.e. thick enough) for the load.
5. Check that all the cables are secured tightly to the connectors.
Use
in the Maintenance and troubleshooting chapter for the correct torque.
Summary of Contents for PODS 16.48-16000 1940 HEX
Page 4: ...1 2 PODS 16 48 16000 1940 HEX Document number titlepage fm Revision B...
Page 10: ...2 6 PODS 16 48 16000 1940 HEX Document number 039158TOC fm Revision B...
Page 23: ...Safety 5 1 Document number 028580 fm Revision A Safety 5 Safety...
Page 40: ...6 14 PODS 16 48 16000 1940 HEX Document number 039160 fm Revision A Installation guide...
Page 41: ...Commissioning 7 1 Document number 036285 fm Revision A Commissioning 7 Commissioning...
Page 92: ...A 10 PODS 16 48 16000 1940 HEX Document number Appendix A fm Revision B Drawings...
Page 94: ...B 2 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...
Page 95: ...Configuration c 000313 B 3 Document number 039418 fm Revision B Configuration c 000313...
Page 96: ...B 4 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...