3.6.
Electrical Connections
Step 1/5: Open the AC grid disconnect switch
Step 2/5: Open the photovoltaic field DC disconnect switch
Step 3/5: Unscrew the 4 captive screws to open the front panel
Step 4/5: Connect AURORA to the AC grid disconnect switch
WARNING:
Use suitable low-impedance cables to connect AURORA
to the AC disconnect switch.
WARNING:
AURORA must be connected to the AC grid disconnect
switch using a three-wire cable with a line wire, a neutral wire and a
yellow-green ground (PE or protective earth) wire.
1)
Route the cable from AURORA to the Ac disconnect
2)
Connect the three-pole cable to Aurora using the cable gland on the
case
3)
Connect the three wires as follows:
-
terminal 1 for Protective earth PE
-
terminal 2 for Neutral N,
-
terminal 3 for Line L,
Fig.11 AC wire terminal block