Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com
9
PFSWCPC75 Series
Submersible Sewage Pumps
Size fuses or circuit breakers according to chart below.
Fuse Data
MODEL
HP
VOLTAGE
Individual Branch Cercuit
Required (Amps)
PFSWCPC75201451F10
3/4
115
20
PFSWCPC75201451T10
PFSWCPC75201452F10
230
10
PFSWCPC75201452T10
OPERATION
NOTICE:
Do not allow pump to run in a dry sump. It will void the warranty and may damage the pump.
An automatic overload protector in the motor will protect motor from burning out due to overheating / overloading. When motor
cools down, overload protector will automatically reset and start motor. If overload trips frequently, check for cause. It could be a
stuck impeller, wrong/low voltage, or electrical failure in motor. If an electrical failure in the motor is suspected, have it serviced by
a competent repairman.
Pump is permanently lubricated. No oiling or greasing is required.
Operation
Figure 1 - For 115 Volt
Figure 2 - For 230 Volt